PN: 002-00095-00 | Rev. 1.1 | Oct. 26, 2022

TS4-A-2F Quick Start Guide

Pg 2 of 2

3. Commissioning

!

Wear and USE appropriate PPE for the application. Suggestions: gloves, sunscreen,….

!

Wear and USE appropriate PPE for the application. Live voltages may be present.

1.

Each PV string will produce less than 30VDC until the RSS Transmitter is activated/powered.

2.

When power is provided to the RSS Transmitter the PV strings will produce full voltage under the
environmental conditions.

3.

Commission the PV system as per best practice.

3.1 Pre-commissioning checklist

3.2 Commissioning notes

Issue

Check

No string voltage

Check that all string connectors are securely connected.

Lower voltage than
expected

Check that all PV module connectors are securely connected.

Note

– with no keep-alive signal the string voltage will less than 30VDC.

Check that the RSS transmitter is powered on. If multiple transmitters are used, check that all
are of the Pure Signal Technology (PST) series and are properly wired.

Inconsistent
voltage reading
when no signal is
present

1.

Apply power to the RSS Transmitter

2.

Use an RSS Signal Detector to determine if the individual TS4s are receiving the keep
alive signal. If so, check the string is less than 300m.

4. Troubleshooting

5. Your Customer Service Contact

United States (HQ):

Tigo Energy, Inc.

655 Campbell Technology Pkwy
Campbell, CA 95008

EMEA Office:

Tigo Energy Italy

Srl Via Calamandrei 36 52025
Montevarchi Tuscany, Italy

Americas: +1 408 402 0802
International: 00800 2255 8446

https://support.tigoenergy.com/

Class II double insulation

High Voltage

DANGER

Check Item

Acceptance Criteria

TS4 installation

All PV modules are connected to a TS4-A-F/TS4-A-2F.

Tigo RSS
Transmitter/PST

The Tigo RSS Transmitter is installed per the RSS Transmitter Installation Manual. If
inverter integrated, follow the inverter manufacturer’s instructions for signal/power.

Voltage check

The TS4-A-2F passes 0.6VDC at the output to the string.
String voltage = 0.6VDC x # TS4s in the system.
If TS4-A-F are also used in the same string, add 0.6V for each additional TS4-A-F.

Connections

All connectors are securely mated and of same type.

Wire Management

All conductors are properly secured throughout the array. ANSI/NFPA 70 wiring methods
used. Multi transmitter systems have PST transmitters installed and properly wired. Refer
to RSS Transmitter Installation manual for details.

Workmanship

Wire management and general best practices were used.