TIF TIF900 User Manual Download Page 13

  TIF900

 

 

EN - 12

4.6. M

INSULATION RESISTANCE MEASUREMENT TEST VOLTAGE 250V, 
500V, 1000V DC 

The measurement is performed according to EN 61557-2 and VDE 0413 part 1. 

 

 

 

CAUTION 

 

 

 

 

  before performing the insulation test make sure that the circuit under test is 

not energized and all relative loads are disconnected 

  the insulation measurement requires particolar care and attention to avoid 

providing wrong test results and causing damages to third parties 

  before the insulation test prepare the plant adequately by disconnecting 

everything must not be tested. During the insulation test continuously make 
sure that the applied voltage is not accessible to third parties 

 

a measurement with a cable disconnected by mistake may provide a good 

result also in presence of a faulty insulation. It’s necessary to take all 
possibile cares to avoid that. Once prepared the plant and connected the 
measuring cables, make sure that they are correctly connected. In case of 
doubt, bifore performing an insulation test, perform a 

 0.2A measurement 

by short-circuiting the cables under test at a point of the plant which is as 
far as possibile from the measuring clips. Remove the short circuit before 
performing the insulation test

 

 

 

Fig. 8: Connection of the instrument’s terminals during M

 test 

 

 

 

1. 

 

Turn on the instrument 

 

 

 

2. 

 

Press the arrow keys to select 

M

 

 

 

 

3.  Insert the black and red cables in the corresponding input terminals of the instrument 

 

 

 

4.  If the cable length is not sufficient for the measurement extend the black one with an 

adequately insulated cable, as its insulation is in parallel to the resistance to be measured. It 
must be suspended and not laid to earth and all supports must be of insulated material 

 

 

 

5.  If necessary insert the croco clips on the test probes 

 

 

 

6.  Disconnect the circuit or the part of plant under test from power and all eventual loads 

 

 

 

7.  Connect the instrument’s terminals to the end of the conductors on which the insulation test 

must be performed (see Fig. 8) 

 

 

 

8. 

GO

 

Press 

GO

 to start the measurement for the set time (see par. 4.6.1). Press 

GO

 

to stop the measurement before the end of the set time 

Summary of Contents for TIF900

Page 1: ...Copyright Advanced Test Products 2011 Release EN 11 TIF900 Insulation Tester User s manual...

Page 2: ...measurement and continuity test 8 4 4 1 ZERO mode 8 4 4 2 Anomalous cases which may occur during measurement 9 4 5 Lo Continuity test on earth protective and equalizing potential conductors 10 4 5 1...

Page 3: ...g pools etc and 50V in ordinary places to avoid risks of electrical shocks The following symbols are used CAUTION refer to the instruction manual an improper use may damage the instrument or its compo...

Page 4: ...SIS Circuits are divided into the following measurement categories Measurement category IV is for measurements performed at the source of the low voltage installation Examples are electricity meters a...

Page 5: ...to shipment All possible cares and precautions were taken to let you receive the instrument in perfect conditions Notwithstanding we suggest you to check it rapidly eventual damages may have occurred...

Page 6: ...all display segments are lit for just a while Then the instrument is ready for DC voltage measurement 4 1 2 Auto power off The instrument automatically turns off 15 minutes after last pressure of keys...

Page 7: ...erminals of the instrument 4 If necessary insert the croco clips on the test probes 5 Connect the cables to the desired points of the circuit under test as shown in Fig 2 The voltage value will be dis...

Page 8: ...erminals of the instrument 4 If necessary insert the croco clips on the test probes 5 Connect the cables to the desired points of the circuit under test as shown in Fig 3 The voltage value will be dis...

Page 9: ...test see Fig 4 6 GO Press GO to perform the measurement 7 Example of display of resistance value If such value is lower than 30 the instrument emits an acoustic signal 8 GO Press LOCK and GO together...

Page 10: ...ts performed until a new pressing of the ZERO key for 2s that voids the calibration 6 Each time the instrument is switched off or changing position of selector the calibrated value is lost 4 4 2 Anoma...

Page 11: ...ut terminals of the instrument Resistance value 4 If the measuring cables being used have not been calibrated first calibrate them as described in paragraph 4 5 1 5 Position the test probes on the des...

Page 12: ...ment and used as offset which means it s deducted from all continuity tests performed until a new pressing of the ZERO key for 2s that voids the calibration 6 Each time the instrument is switched off...

Page 13: ...doubt bifore performing an insulation test perform a 0 2A measurement by short circuiting the cables under test at a point of the plant which is as far as possibile from the measuring clips Remove th...

Page 14: ...ion value generally much higher than the minimum requirements prescribed by standards 12 GO Press LOCK and GO together to perform the measurement in continuous mode the symbol LOCK is displayed Press...

Page 15: ...terminals to avoid electrical shocks 1 Switch off the instrument 2 Remove test leads from the input terminals 3 Remove the battery compartment cover by using a screwdriver 4 Remove all batteries repl...

Page 16: ...e Resolution Accuracy Overload protection 0 00 19 99 0 01 2 0 rdg 3 dgt 605V max RMS Test current 200mA DC up to 5 measuring cables resistance included Test current 10mA DC over 5 measuring cables res...

Page 17: ...y life Multimeter About 50 hours Lo 1000 tests 1 M 250V 1000 tests 480k M 500V 1000 tests 480k M 1000V 1000 tests 480k Display Features 4 LCD with max reading 9999 counts symbol and decimal point 6 2...

Page 18: ...t Repairs made necessary by previous attempts for repair carried out by non skilled or unauthorized personnel Instruments for whatever reason modified by the customer himself without explicit authoriz...

Page 19: ...TIF900 EN 18...

Reviews: