TIANJIN BAILI ERTONG MACHINERY NQB1 Operation Manual Download Page 6

be kept in dry environment if it cannot be mounted immediately. Don’t remove the sealing plug 
before finishing connecting the wire so as to prevent the sealing performance from being 
damaged. 
          2. The internal grounding and external grounding of the electric actuator shall be fastened 
and reliable. 
          3. Cable shall be correctly connected to avoid the rain leaking into the electric actuator (the 
first two connection patterns are right in the following picture.)   

 

 

 

 

 

 

 

 

 

 

 

4.Product debugging 

4.1 Adjustment 

The torque control mechanism has been tested and standardized before factory delivery. The 

output torque complies with the maximum control torque shown on the nameplate, so users do not 
need to re-adjust. Besides, the two mechanical limit screws on the product body have been 
adjusted and fastened. Don’t loosen it even in special case. 

The cams and dials of the drive shaft, stroke control and position indication mechanism are 

normally set at the “CLOSE” position, it is unnecessary to change the position of the dial in order 
to be easy for observation when carrying out installation and commissioning.     

The potentiometer gear and the potentiometer shaft are under loosened state, preventing the 

potentiometer from being damaged during commissioning.   

The cam on top of the stroke control mechanism is used to control “open” of the valve, and 

the cam on the bottom is used to control “close” of the valve.   

The adjustment of stroke control and position indication mechanism:   

4.1.1 Operate the valve manually to the neutral position.   
4.1.2 Start the electric actuator; confirm that movement direction of the valve matches to the 

control when it is electrically controlled. If there is any error, change the phase sequence of the

 

power supply (this operation is not required for the integral type electric actuator equipped with 
automatic phase changing function).   

4.1.3 Manually operate the valve to “CLOSE” position; loosen the screw on the “CLOSE” 

stroke cam; rotate the cam in the direction of closing the valve to make it touch the roller and 
contact of the corresponding micro switch. When “click” from the micro switch is heard, the 
screw on the cam can be tightened properly.   

4.1.4 Manually operates the valve towards the open direction, causing the “CLOSE” stroke cam 

to disengage from the roller and probe of the micro switch. And then, operate the valve towards 
the close direction of the valve electrically to inspect the correctness of the valve “CLOSE” 
position adjustment. If the control is correct and the action is sensitive, the adjustment is 
acceptable. At this time, tighten the screw on the cam of “CLOSE” stroke reliably, no looseness is 
allowed. If there is error with the valve “CLOSE” position, adjust the cam finely, and repeat the 
inspection of the adjustment correctness until it is OK.   

4.1.5 Operate the valve to “OPEN” position manually; loosen the screw on the “OPEN” stroke 

Summary of Contents for NQB1

Page 1: ...0 SM 20 Please read this Operation Manual carefully before using this product NQB1 NQB2 Quarter turn electric valve actuator Operation Manual TIANJIN BAILI ERTONG MACHINERY CO LTD ...

Page 2: ...Content 1 Product instruction 1 2 Product mounting 2 3 Electric wiring 3 4 Product debugging 4 5 Additional instruction for explosion proof type 5 6 Precautions 7 ...

Page 3: ...elp to ensure that product mounting debugging and maintenance are dealt in right ways Please refer to Fig 1 Fig 4 for product outline For the dimension of the flange coupling with valve the dimension of driving shaft s whole and key refer to the Catalogue of the manufacturer Notify the specific technical parameters when ordering Please refer to product s nameplate for driving output power of the e...

Page 4: ...echanism will return to the electrical position When pushing the switching handle arm the handle may be rotated properly to make the internal mechanism engaged 1 4 6 Mechanical limit mechanism used to restrain the limit position of the output shaft Since it has been adjusted before factory delivery it should not be loosened at will in case of over adjustment disengage the worm segment and worm The...

Page 5: ...e of cables with connection wiring terminal board 3 and wiring should be reliable and shall not be exposed Pull the cable outwards in a proper amount to ensure it will not interfere with other operating components in the cavity Rotate the input sealing wire plug into the thread hole of the case body firmly screw the gland nut on the sealing wire plug so as to ensure the sealing performance of cont...

Page 6: ...and the cam on the bottom is used to control close of the valve The adjustment of stroke control and position indication mechanism 4 1 1 Operate the valve manually to the neutral position 4 1 2 Start the electric actuator confirm that movement direction of the valve matches to the control when it is electrically controlled If there is any error change the phase sequence of the power supply this op...

Page 7: ...er to the nameplate of the electric actuator is OPEN limit and CLOSE limit for the other one After the end position of the valve is decided adjust the screw inwards to make it contact with the limit section on the drive shaft first and then rotate it back by 0 5 to 1 turns At last tighten the retention screw or nut at outside this completes the adjustment of mechanical limit Note The limit screw i...

Page 8: ...nameplate For the outline dimension flange dimension connected with valve and the position and dimension of inlet wire position of explosion proof wiring box please refer to the catalogue from our Company 5 2 Notice for usage and maintenance Refer to Fig 1 for the structure 5 2 1 Power must be cut off when actuator s any cover is open Please see the warning plate Forbid to open the box cover when ...

Page 9: ...perating condition to determine whether to replace or replenish 6 3 After this product is removed from the valve for repairing or replacing the lubrication grease the stroke control and position indication mechanism should be inspected and adjusted The torque control mechanism should be inspected and calibrated if necessary making it be in accordance to the requirement 6 4 When using in the enviro...

Page 10: ...8 Fig 1 Fig 3 Fig 2 ...

Page 11: ...9 Fig 4 ...

Page 12: ...d hole size and their positions should be specified Whether the hole for stem is required or not should be clarified Specify whether there is a special requirement or not such as explosion proof Introduce the operation condition in brief The controller should be specified separately when placing an order TIANJIN BAILI ERTONG MACHINERY CO LTD Address Block B No 180 Hanghai Road Tianjin Pilot Free T...

Reviews: