Please read this user manual carefully before installation.

TCMK5413W Wireless Input&Output Module

User Manual

Liaoning·Tiancheng Fire Protection Equipment Co., LTD

Summary of Contents for TCMK5413W

Page 1: ...Please read this user manual carefully before installation TCMK5413W Wireless Input Output Module User Manual Liaoning Tiancheng Fire Protection Equipment Co LTD ...

Page 2: ...Version Date Author Note Ver1 0 202009 Nov 16 2020 Deng Yi Yan Chong Create ...

Page 3: ...ce will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect t...

Page 4: ...ic interference III Technical specifications 1 Battery type CR17450 wired 2 Rated working voltage 3 0V 3 Working Current Standby Current 14uA Alarm Current 10mA 4 Indicators Input light red always on when there is an input signal Output light red always on when output action Fault Indicator yellow flashing when the module is faulty Working Indicator Green flashing when communication is normal Note...

Page 5: ...utline dimension 101mm 137mm 43mm 12 Material and color ABS off white 13 Weight about 170g including battery 14 Executive standard GB 16806 2006 Fire Linkage Control System XF 1151 2014 General Requirements for Wireless Communication Functions of Fire Alarm Systems IV Structure characteristics and working principle 1 The outline diagram of the module is shown in Figure 1 Figure 1 Outline diagram o...

Page 6: ...l to connect to other devices and the module output red light is always on When the module battery is low the module sends a battery undervoltage signal to the control panel and the fault yellow light flashes 3 Installation method 1 Before installation first check whether the shell is intact and whether the identification is complete 2 Module fixing method When installing use two screws to fix the...

Page 7: ...JTY GM TC5401W 无线点型光电感烟火灾探测器安装使用说明书 Ver1 0 202010 辽宁 营口天成消防设备有限公司 5 Fig 3 Installation hole distance AS1 AS2 Passive answer signal input OUT1 OUT2 Passive normally open output Fig 4 Wiring diagram ...

Page 8: ... is in the wireless registration interface and the module is not connected to the network quickly press the Settings button 3 times and the green light flashes 3 times the module sends a network access application to the control panel application After success the total number of network access displayed by the control panel 1 B Network exit operation When the control panel is in the wireless regi...

Page 9: ...ng button 3 times to turn off the output fault detection and the yellow light will flash 3 times when the setting is successful Note If the output failure detection has been set to turn off the above operation can turn on the failure detection VII General failure and repair General faults and their solutions are shown in the table below Fault Reason Solution Faulty yellow light flashes once every ...

Page 10: ...eatly attenuated so try to reduce the number of partition walls for wireless products 2 When installing the product keep it away from metal to reduce the shielding of metal objects to the signal For example it cannot be installed in a metal box such as a fire hydrant box or outside of a metal cabinet 3 Install in a low interference environment and far away from motors or large scale electrical equ...

Page 11: ...消防设备有限公司 9 Liaoning Yingkou Tiancheng Fire Equipment Co Ltd Address No 11 2 Kechechang Xili Xishi District Yingkou Pilot Free Trade Zone Liaoning China City Fax 0417 4835568 Postcode 115004 Tel 400 6930 119 Email info tcfiretech com Website www tcfiretech com ...