MEASURES, LOGIC STATES AND COUNTERS
134
NA30 - Manual - 04 - 2022
Example 1
With the following setting:
• Pre-trigger:
0.25 s
• Post-trigger:
0.25 s
• Sampled measures:
i
L1
,
i
L2
,
i
L3
,
i
E
• Analog measures:
I
L1
,
I
L2
,
I
L3
,
I
E
• Logic variables:
K1, K2, K3, K4, K5, K6, IN1, IN2
up to record can be stored if f = 50 Hz, since:
Example 2
With following setting:
• Pre-trigger:
0.5 s
• Post-trigger:
0.5 s
• Sampled data:
i
L1
,
i
L2
,
i
L3
,
i
E
• Analog channels:
I
L1
,
I
L2
,
I
L3
,
I
E
• Digital channels:
K1, K2, K3, K4, K5, K6, IN1, IN2
up to 75 records can be stored if f = 60 Hz, since:
= 180
(34 + 20 · 4 + 4 · 4 + 2) · (0.25 + 0.25)
N
= int
12000
· 50 (Hz)
50 (Hz)
= 75
(34 + 20 · 4 + 4 · 4 + 2) · (0.50 + 0.50)
N
= int
12000
· 50 (Hz)
60 (Hz)
oscillo-phase.ai
Phase/to/phase fault record