TECHNICAL DATA
15
NA011 - Manual - 05 - 2022
3.4 MMI
Display
16x2 LCD backlight module
LEDs
Quantity
8
• ON/fail (green)
1
• Start (yellow)
1
• Trip (red)
1
• Trip I>, I>>, I>>> (red)
1
• Trip IE>, IE>> (red)
1
• 52a - Circuit Breaker closed (red)
1
• 52b - Circuit Breaker open (red)
1
• 79 - Automatic reclosure (red)
1
Keyboard
8
keys
3.5 COMMUNICATION INTERFACES
Local port
Connection
RJ10
Baud rate
19200 bps
Parity None
Protocol Modbus
RTU®
Remote ports
RS485
• Connection
screw terminals
• Baud rate
1200...57600 bps
• Protocol
ModBus®RTU
IEC 60870-5-103
3.6 GENERAL SETTINGS
Relay nominal frequency
f
n
50, 60 Hz
Phase CT primary nominal current
I
np
[1]
1 A...5000 A
1...99 A (step 1 A)
100...5000 A (step 5 A)
Residual CT primary nominal current
I
Enp
[2]
1 A...1000 A
1...99 A (step 1 A)
100...5000 A (step 5 A)
3.7 PROTECTIVE ELEMENTS
Phase overcurrent - 50/51
I> Element
I
> Curve type (
I>
Curve
)
DEFINITE,
IEC/BS A, B, C,
ANSI/IEEEE MI, VI, EI, I2T
CLP Activation time (
t
CLP>
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
I
> Reset time delay (
t
>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
50/51 First threshold definite time (
I
>
def
) 0.100...20.0
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...9.99
I
n
(step 0.01
I
n
)
10.0...20.0
I
n
(step 0.1
I
n
)
I
>
def
within CLP (
I
CLP>def
) 0.100...20.0
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...9.99
I
n
(step 0.01
I
n
)
10.0...20.0
I
n
(step 0.1
I
n
)
I
>
def
I
>
def
Operating time (
t
>
def
)
0.03...10.00 s (step 0.01 s)
Note 1 The rated phase current settings doesn’t concern the 50/51 protection elements; they must agree with nominal primary current for traditional CT
inputs or dip-switch 50...1250 A for LPCT inputs for a right reading of the phase current primary values (Reading Direct).
Note 2 The rated residual current settings doesn’t concern the 50N/51N protection elements; they must agree with nominal primary current of the CT
inputs for a right reading of the residual current primary values (Reading Direct).
For the NA011#xxx0 and NA011#xxx1 versions (no residual current input circuit), the parameter is meaningless