5.
Dimensions
(All Dimensions in mm) – Subject to Alterations
6.
Assembly and Installation
6.1
Electrical Connection
6.1.1
Cable Entries through Top Cover
F
Loosen the M4 set screw of Top Cover of the
luminaire. (Figure 1)
F
Loosen the Top Cover of the luminaire and
remove it.
F
The thread of cable entry hole of Top Cover is
NPT 3/4” or M20.
F
Attach the Top Cover to suitable conduit.
F
Insert the cable from outside through the conduit
and the cable entry hole of Top Cover.
F
Introduce the wires of the luminaire with wires of
cable by attached closed-end-terminals as
following (Figure 2):
Black-wire connects to Neutral;
Red-wire connects to Live;
Green-wire connects to Ground.
F
Thread the Top Cover and torque until
wrench-tight.
F
Tighten the M4 set screw of Top Cover with
torque value 1 N-m.
F
Check the tightness of conduit and Top Cover.
6.1.2
Cable Entries through Entry Hole of Tank
F
Loosen the Plug from the Tank and remove it.
(Figure 3)
F
The thread of cable entry hole of Tank is M20.
F
Attach the Tank to suitable conduit.
F
Insert the cable from outside through the conduit
and the cable entry hole of Tank.
F
Introduce the wires of the luminaire with wires of
cable by attached closed-end-terminals as
following (Figure 2):
Black-wire connects to Neutral;
Red-wire connects to Live;
Green-wire connects to Ground.
F
Thread the conduit and torque until wrench-tight
with torque value 40 N-m.
F
Check the tightness of conduit.
6.2
Mounting Bracket Installation
6.2.1
Wall Mounting & Pendant Mounting Bracket (W25, W90 & H25, H90)
F
The mounting bracket is both for the use of wall
mounting and Pendant mounting.
F
Position the bracket holders and fix it by means of
the provided M6 screws, 24.5 kgf-cm. (Figure 4)
F
Secure the wall/pendant mounting bracket to the
structure by using six fasteners (not provided).
(Figure 5)
F
The lighting can be adjusted up and down by 25°.
Red: Live wire
Green: Ground wire
Black: Neutral wire
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5