IMA 212 

Rev 

Page 
3 (4)

 

 

Electrical connections  

 

The power supply has to be connected to 

+~ 

and 

 is considered as system 

ground.  The same ground reference has to be used for  the  CF3-W-US-Disp-FLI  unit 
and for the DDC/signal receiver.
   

 

PLEASE NOTE! The same ground reference has to be 
used for the 
CF3-W-US-Disp-FLI unit and for the control 

system!

 

 

Terminal 

Function 

Electrical data 

Remarks 

+~ 

 
 

 

Power (+) 

 
 

Power ground (-) 

24 VAC/DC+  (+-20%), 

2W 

 

24 VAC/DC- 

 
 
 
System voltage reference 

OUT1 

 
 

OUT2 

 

Analogue output 

1 (+) 

 

Silences the 

acoustic alarm  

0-10 VDC 

 

 

0-2000 ppm CO

2

 

 
A push on the push button 
silences the acoustic alarm 
for 30 minutes. 

Table I. Connections of the main terminal of CF3-W-US-Disp-FLI

  

 

LED Colour 

Electrical data 

Remarks 

Green 

0VDC 
 
10VDC 

 
 
Lit between 0-800 ppm CO

2

 

Yellow 

0VDC 
 
10VDC 

 
 
Lit between 800-1400 ppm CO

2

 

Red 

0VDC 
 
10VDC 

 
 
Lit above 1400 ppm CO

2

. Buzzer sounds. 

Table II. The LEDs

 

 

Self-diagnostics 

The system contains complete self-diagnostic procedures that are executed 
automatically when the sensor is in operation. Sensors with display show a wrench if 
an error is found. The wrench is shown during the first seconds after power up and if 
the measuring range is exceeded.  
 

Maintenance 

The  CF3-W-US-Disp-FLI  is basically maintenance free  in normal environments 
thanks to the built-in self-correcting ABC algorithm. 
 
PLEASE NOTE!  The sensor accuracy is defined at continuous operation (at 
least 3 weeks after installation) 
 
Electronic products should be disposed of via a suitable recycling centre. 

 