background image

Installation

ULTRAFLOW® 54 

DN150-250

 

Tel: 

+44

  

(0)191 490 1547 

Fax: 

+44

 

(0)191 477 5371

 

Email: 

[email protected]

  

Website: 

www.heattracing.co.uk 

                  www.thorneanderrick.co.uk

 

Summary of Contents for Kamstrup ULTRAFLOW 54

Page 1: ...Installation ULTRAFLOW 54 DN150 250 Tel 44 0 191 490 1547 Fax 44 0 191 477 5371 Email northernsales thorneandderrick co uk Website www heattracing co uk www thorneanderrick co uk...

Page 2: ...2...

Page 3: ...cal connection 11 2 1 Connection to calculator 11 2 1 1 ULTRAFLOW 54 and MULTICAL galvanically coupled 11 2 1 2 ULTRAFLOW 54 and MULTICAL galvanically separated 11 2 2 Connection of power supply 13 2...

Page 4: ...4...

Page 5: ...r battery supply a lithium battery with connector from Kamstrup A S must be used Lithium batteries must be correctly handled and disposed of see Kamstrup document 5510 408 Lithium batteries Handling a...

Page 6: ...sor tube will thus be vertical which is optimal in connection with possible stratification of the medium Figure 1 1 1 1 Mounting ULTRAFLOW 54 in lifting ring ULTRAFLOW 54 can be mounted hanging from o...

Page 7: ...the box approx 170 mm away from the flow sensor housing Alternatively a shorter distance piece which only moves the box approx 45 mm away from the flow sensor housing can be used The short distance p...

Page 8: ...ays point downwards see paragraph 1 2 1 Orientation of flow sensor electronics box page 9 Alternatively the electronics box can be wall mounted as long as the distance to flow sensor housing and pipe...

Page 9: ...the electronics box via the cables This is especially important in humid environments when ULTRAFLOW 54 is used as cooling sensor or if the medium temperature can become more than 5 C lower than the...

Page 10: ...ceptable in closed systems Unacceptable position in open systems due to risk of air build up in system E A flow sensor ought not to be placed immediately after a valve with the exception of block valv...

Page 11: ...nd MULTICAL are connected via output module Y 1 ULTRAFLOW 54 is galvanically coupled with the MULTICAL calculator and is powered by the calculator via the three wire signal cable cable length up to 10...

Page 12: ...5 metres Diagram 3 Two wire connection MULTICAL 801 via output module Y 2 Cable length up to 100 metres Diagram 4 Two wire connection MULTICAL 602 D via output module Y 2 and external 24 VDC supply Ca...

Page 13: ...laced by a corresponding lithium battery with connector from Kamstrup A S Used batteries must be handed in for approved destruction f inst at Kamstrup A S See Kamstrup document 5510 408 Lithium batter...

Page 14: ...fixed 230 24 V installation in the main electrical panel must only be carried out by an authorized electrician Note This module cannot be supplied by 24 VDC direct current 230 24 V safety transformer...

Page 15: ...company change Thus it can be an advantage to change mains supplied meters to battery meters in buildings under construction where the mains supply can be unstable or periodically missing Please note...

Page 16: ...orward and return pipes are not necessarily closely coupled Electric welding can occur Electric welding must always be carried out with the earth pole closest to the welding point Damage to meters due...

Reviews: