SENSA MSF SEND DSI (96013491) & SENSA MSF SEND DALI (96238878)

Only suitably qualified personnel should install this equipment.

Fixing

The housing may be secured to a hard surface or a BESA box.   The unit fits into the housing with a simple 
bayonet action. 

NOTE:

 Do not position within 25cm of a luminaire.

Connection

A 10A type C MCB is recommended for the supply.  A means for disconnection must be incorporated in 
the fixed wiring according to the wiring regulations.

Control of a group of luminaires is achieved via the detector’s two-wire digital control circuit.  Each luminaire to be 
controlled must contain a digital regulating type ballast with the appropriate DSI input (for use with 96013491) or 
DALI input (for use with 96238878). Ballast types must not be mixed. Connect all ballasts in the control group 
(max 8) in parallel and also to the polarity-free digital output of the detector.

Each luminaire is controlled completely by its digital input and therefore would normally have a permanent power 
supply.  If, however, it is desired to have manual wall switches, any or all of the fittings in a controlled group may 
also be controlled in the traditional way - by turning off the power.   The control circuit will continue to operate 
properly even if some of the luminaires in the group have had mains power removed.

        Dimming

         dimming affords local control to the end-user whereby a simple, momentary, push-to-make wallswitch can 
be used to raise or lower the lighting level or to toggle the output ON/OFF. A short press of the switch (less than    
1 second) will toggle the output status while a longer press will raise or lower the output. Each time the switch is 
pressed, the direction of dimming reverses. If the switch has not been pressed for 5 seconds, the direction will 
be up (brighter) - unless the output is already above 90% in which case the direction is down. If the switch is held 
continuously, and the output reaches maximum, the light output will remain at this level until the switch is 
released - a latching switch may be connected in parallel allowing the occupancy detection to be overridden on 
(Note: If the initial direction was down, when the output reaches minimum it will ramp back up automatically). 

Important Additional Notes

1.

All terminals on this product are provided for final connections.  It is not intended that the product be used as a junction box 
for looping cables.

2.

A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.

3.

Although nominally 12V, the dimming output is not ELV and therefore should be treated with the same respect as mains with 
regard to wiring practice.  The 0V line of the dimming output is almost at Neutral potential.

4.

The dimming control output should be connected only to the control input of the ballasts - never to other detectors.

5.

This equipment should be used to control only those ballasts powered from the same phase as the detector.

6.

Due to the fact that the photocell is on the ceiling looking down, it is not possible for measurements made with a lux meter on 
the working plane to remain constant when daylight illuminates the ceiling and the working plane to a differing extent.   
Therefore, products of this type should be regarded as capable of maintaining an APPROXIMATE light level only.

W4335C

Setting the regulating photocell

This product is intended for use with high frequency regulating ballasts with DSI or DALI control inputs.   An 
infrared programming tool SENSA SENP (96004189)  is required for programming the regulating light level set 
point.  The setting is preserved in the event of a power failure and can be re-programmed any number of times.  

Use the ‘up’ and ‘down’ buttons to manually adjust the light output from the luminaire(s) and when at the required 
level press and hold the ‘store’ button. The luminaire(s) will blink to acknowledge a successful store operation.  

Commissioning

The factory default settings will be appropriate for most applications.  However, the installer does have the facility 
to re-programme a wide range of parameters and to set the regulating light level using the infrared programming 
tool, SENSA SENP (96004189). 

Please  read  carefully  the  operating  instructions  that  accompany  the  SENSA  SENP  (96004189)  prior  to 
performing a programming operation.

Below is a table showing the pre-set factory settings and a brief explanation of each parameter. These parameters 
may be re-programmed any number of times and all settings will be retained in the event of a power loss.

T

T

Parameter

Options

Pre-set

Notes

Power up

on/off

on

Sets the luminaire state at power up irrespective of occupancy.  Useful in 
reducing start-up load following power cut.  Power-Up off - responds to 
occupancy after 30 seconds.

Response

auto/semi-auto

auto

If set to auto, the presence detector switches the luminaire on and off 
automatically. If set to semi-auto, the luminaire will not turn on automatically 
when a person enters the area.  It can be turned on using the hand-held 
controller or by toggling the power switch.  When the area is  vacated, the light 
will turn off automatically.

Off delay 

5 - 35 mins

20 mins

The time for which the luminaire will stay on following the last detected 
movement.  Also 10 second setting for walk-testing.

Start lamps

max/min

max

Sets the level at which the lamps strike when turning on.

Bright out

yes/no

no

If set to yes, movement fails to refresh the off delay if the ambient light level 
exceeds 125% of the set level,  and the luminaire will switch off when the 
the off delay has elapsed. (Note Dimming must be set to 100%)

Fade to off

yes/no

no

When no presence is detected, and after the off delay period, the lamps can 
fade out instead of switching off (approx 80 seconds to fade from100% to 0%).

When vacant

low/off / reg <25%

off

These are the options for a vacant area after it has timed out.  Luminaires can 
turn off, remain at minimum output, or regulate with a 25% output limit, until  
the next period of occupancy. If programmed to remain at minimum or regulate 

 

below 25%, there is a programmable option to switch off after 3 times the Off 
delay.