Thorn SENSA MSF SEND DSI Installation And Commissioning Instructions Download Page 1

At the end of their useful life 
the packaging and product 
should be disposed of via a 
suitable recycling centre.
Do not dispose of with normal 
household waste.
Do not burn.

Installation and Commissioning

Instructions

Electrical Connections

Dimensions

SensaDigital Detector, 

ceiling mounted, surface

SENSA MSF SEND DSI (96013491)

SENSA MSF SEND DALI (96238878)

Thorn Lighting Limited
www.thornlighting.com

Input

L

N

230V 50Hz
Mains Supply

T

DSI out (96013491)
DALI out (96238878)
Polarity-free; do not connect to other detectors.

Flange: 10mm deep

100mm

62mm

deep

Technical Data 

   

RECOMMENDED MAXIMUM MOUNTING HEIGHT: 3.0m
RANGE: Cone-shaped detection pattern, diameter (at floor level) = 2.4 x mounting height

OPERATING VOLTAGE: 230V 50Hz 
PRODUCT RATING & RECOMMENDED CIRCUIT PROTECTION: 10 Amps
CAPACITY: 8  ballasts 
OUTPUT: 2-wire digital polarity free
PHOTOCELL: Regulating
OFF DELAY: 5-35 minutes
WEIGHT: 200g approx
COLOUR: White
MATERIAL: Flame retardant PC/ABS
IP RATING: IP 40

6.0m

2.5m

Note: SENSA SENP required for commissioning

W4335C

(see overleaf)

Push-to-Make

Mains-Rated

Retractive Switch

Reviews: