EAP 300 REMOTE ANNUNCIATOR 

 

PM084 REV 0  08/06/20                                                                                                                   THOMSON TECHNOLOGY   

 

2

 

2.  DESCRIPTION 

 
The  annunciator  panel  (EAP  300)  which  can  be  connected  to  the  MEC  310  via  a  CANbus 
communication line. The EAP 300 has 16 configurable LEDs and 8 configurable buttons, which are 
programmed with the TPS 300 PC utility software. It can be used as an interface to the MEC 310 for 
indication of status and alarms together with buttons for e.g. remote alarm acknowledge and mode 
selection. 
 

Contents: 

A DC/DC converter for the EAP 300 DC supply voltage and cable with an RJ12 plug in one end and 
stripped wires in the other end is included in the EAP 300 Kit. 
 

NOTE:

  

A maximum of 2 EAP 300 units can be connected 

to each MEC 310. 

 

NOTE:

  

The maximum length of the CANbus line is 200m. 

 
 
 

REAR VIEW 

 
 
 
 
 
 
 
 
 
 
 
 
 
Connectors: 

 
CAN 1:   

DC supply (input) and CANbus communication to/from MEC 310 or other EAP 300 
units. 

CAN 2:   

CANbus communication to/from other MEC 310 or EAP 300 units and status relay 
output. 

End resistor:  

Dip  switch  for  120 

  end  resistor  for  the  CANbus  communication. 

Dip  switch  2  is 

not used 

Torque:  

4 lb-in 

 
 
 
 

EAP 300 

Summary of Contents for EAP 300

Page 1: ...Street Langley BC Canada V1M 3B1 Telephone 604 888 0110 Telefax 604 888 3381 E Mail info thomsontechnology com www thomsontechnology com EAP 300 REMOTE ANNUNCIATOR INSTALLATION MANUAL r 0454A PM084 Re...

Page 2: ......

Page 3: ...CONTENTS 1 WARNINGS AND LEGAL INFORMATION 1 LEGAL INFORMATION AND RESPONSIBILITY 1 ELECTROSTATIC DISCHARGE AWARENESS 1 SAFETY ISSUES 1 FACTORY SETTINGS 1 DEFINITIONS 1 2 DESCRIPTION 2 REAR VIEW 2 3 IN...

Page 4: ...in working with live electrical equipment Factory settings The unit is delivered with certain factory settings Given the fact that these settings are based on average values they are not necessarily...

Page 5: ...knowledge and mode selection Contents A DC DC converter for the EAP 300 DC supply voltage and cable with an RJ12 plug in one end and stripped wires in the other end is included in the EAP 300 Kit NOTE...

Page 6: ...3 3 INSTRUCTIONS FRONT VIEW The configurable LEDs are named 1 to 16 Buttons are named 1 to 8 INSTALLATION Mount on a flat surface of a Type 1 Enclosure Note the maximum ambient temperature rating is 6...

Page 7: ...is ON Thus the dip switch is at the right position if only one EAP 300 is connected If there are two EAP 300 s connected the end resistor of the EAP 300 with a connector plug in both CAN 1 and CAN 2 m...

Page 8: ...eturn to normal operation Selection of CAN ID CAN ID Indication of CAN ID selection 0 CANbus OFF LED 16 flashes 1 LED 1 light steady LED 16 flashes default value 2 LED 2 light steady LED 16 flashes St...

Reviews: