Chapter 3 Connection
3.1. Preparations
Confirm that the voltage level of discharged battery string is consistent with the discharge tester!
Before connecting to the DFT-6600 Tester, first confirm that the discharged battery string has exited the operating
state and has been disconnected from the charging power and load. Avoid accidents during discharge.
There is enough space around the battery string and the DFT-6600 Tester,
There are No flammable and explosive materials around the site
There are No flammable and explosive gases in the air.
Check that the DFT-6600 Tester is in good condition and that the power switch is in an open state.
There must be no inflammable and explosive materials around the work.
The air must not contain flammable and explosive gases to prevent the occurrence of explosions!
3.2. Host connection
a)
The Air (Control) Switch of the tester back should be in a closed position, if not, please close;
b)
The host power switch is in the off position;
c)
Plug in the host power lead;