
2.0
2.1
INSTALLATION TEST PROCEDURE
INSTALLATION TEST PROCEDURE
(TBM6S ONLY)
TA01977 E Page 4 of 6
CAUTION
Care should be taken to strip the insulation of the conductor
without cutting or nicking the conductor strands, as this
condition will result in premature pull-test failures.
Using a tool that has passed the calibration requirements install a
minimum of six (6) terminals for each die nest on the appropriate
wire for which a performance check is required. In order to obtain
valid and consistent results, perform installation procedure as
follows:
1. Strip conductor approximately 1/4” longer than the connector barrel.
(Strip length for test purposes only. For actual installation, refer to
the instruction sheet supplied with the connectors.)
2. For aluminum conductor, smear a thin layer of joint compound onto
the cable and brush it in
between the strands
with a wire brush or
emery cloth.
3. Insert stripped conductor into connector barrel until it bottoms
out.
4. Choose an installing die with the same color marking as the
connector.
5.
Color-Keyed
®
- Locate connector in die grooves of tool, so that die
is between the color code marks for copper and on the color code
marks for aluminium, see graphics below.
Sta-Kon
®
- Locate
terminal in die grooves of the tool so the die is centrally located
over barrel of the terminal.
NOTE:
Some Color Keyed
®
connectors require more than one
compression. If more than one compression is indicated, the
first compression should be in the indicated area nearest to
the tongue of the terminal and nearest the center of a splice,
and then working progressively toward the end of the barrel.
6. Refer to the instruction sheet supplied with the connectors to
determine the number of required compressions.
7. Squeeze handles fully closed until SHURE STAKE
®
mechanism
releases.
INTERCHANGEABLE
NEST
TYPICAL COPPER
INSTALLATION
TYPICAL ALUMINUM
INSTALLATION
CONNECTOR
FIXED
NEST
CABLE
COLOR CODE
BANDS
INTERCHANGEABLE
NEST
CONNECTOR
CABLE
COLOR CODE
BANDS
FIXED
NEST
2.2
TENSILE TEST PROCEDURE
CABLE
SIZE
MIN. PULL-OUT (lbs.*)
COPPER
ALUMINUM
12
70
35
10
80
40
8
90
45
6
100
50
4
140
70
2
180
90
1
200
100
1/0
250
125
2/0
300
150
3/0
350
175
4/0
450
225
250
500
250
300
550
275
350
600
300
400
650
325
500
800
400
1. Install test sample in a tension-testing machine or a suitable pull-test
fixture.
NOTE:
The pull is to be exerted gradually. An abrupt pull is not a proper test method.
2. Subject each sample to an axial pull which is to be increased until failure of the
connection occurs. See graphics below.
3. The pull force required to separate a terminal from its associated wire shall be no less
than the minimum pullout (see table on the right).
NOTE:
On “C” tap and wire joints, only the smallest wire in each combination is to be
tested for pullout.
EXAMPLES OF TENSILE TESTING MACHINES
1. Ametek Testing Equipment Systems, E. Moline, IL 61244. Mechanical Force Gage Model
No. D-150M, Testing Stand Model No. CTM.
2. John Chatillion & Sons, Kew Gardens, N.Y., N.Y. 11415. Gage Model No. DPPH-100 or
DPPH-200, Testing Stand Model No. HTC.
TERMINAL
FORCE
WIRE
TYPICAL COPPER TEST SAMPLE
TERMINAL
WARNING
SHURE STAKE
®
SAFETY RELEASE
The TBM6S compression tool is equipped with the Shure Stake
®
full stroke compelling mechanism. If it
becomes necessary to release the Shure Stake
®
Mechanism before completion of the crimp cycle, disengage ratchet as follows. Slightly squeeze
handles, and push the dowel pin, releasing the locking mechanism allowing the handles to open.
WIRE
TERMINAL
TYPICAL ALUMINUM TEST SAMPLE
*Conforms to UL and CSA requirements
FORCE
FORCE
TERMINAL
FORCE