background image

 

Complete Solutions in Emergency Lighting   

 

 

      

      STANILITE

 

Complete Solutions in Emergency Lighting   

 

 

      

      STANILITE

© Copyright 2013.  Thomas & Betts Australasia ABN: 062 074 810 898

.                          

 

 

    

     

    Rev: 3.0     26 July 2013     1

© Copyright 2013.  Thomas & Betts Australasia ABN: 062 074 810 898

 

 

 

         

   

Rev: 3.0     26 July 2013     4

Thomas & Betts Australasia. ABN 062 074 810 898

Head Office: Unit D3, 3-29 Birnie Avenue, Lidcombe NSW 2141, Australia

Manufacturing: 23a Nyrang Street, Lidcombe NSW 2141, Australia

Telephone: (+61) 1300 666 595  Facsimile: (+61) 1300 666 594

Remote Power Supply Unit

Installation Manual

GREETINGS

Congratulations on choosing to use this Thomas & Betts product covered by our unique Through-Life Support system. This document is 

designed to assist you during the installation of the product, to ensure the safety of yourself and others.

The Remote Power Supply Unit is designed to be installed quickly and easily however, 

Thomas & Betts recommends that 

you read this document thoroughly before commencing installation.

 This device has been manufactured to provide 

trouble free operation for many years, when treated with due care and maintained through regular and appropriate servicing.

SAFETY WARNING

In Australia and New Zealand, only licensed electricians are permitted by law to work with 240 Volt electrical installations.

Do not attempt to install or connect this product unless you are a licensed electrician.

Turn off and isolate the electrical supply before connecting this fitting to the building wires.

Do not touch the terminals of the terminal block when the light fitting is energised.

The only user serviceable parts are the lamp and battery pack.

Do not tamper with the fitting or the warranty will be void.

As the installer, it is your responsibility to ensure compliance with all relevant building and safety codes, (ie: AS3000, AS/NZS2293).  

Refer to the applicable standards for data and mains cabling installation procedures and requirements.

6.  Lamp operation: 

Maintained:

  Once  powered  up,  in  a  maintained  fitting  the  normal AC  lamp  (if  present)  should  light  up  and  stay  on  until                                 

the power supply to the unit fails. The emergency function of the unit should only operate when the unswitched active power supply 

fails or when somebody presses the manual test button located on the fitting. 

Non-maintained:

 Once powered up, in a non-maintained fitting the present lamp stays off. The emergency function of the unit 

should only operate when the unswitched active power supply fails or when somebody presses the manual test button located on 

the fitting. 

TO REMOVE INSTALLED UNIT

Switch off the mains supplies to the unit. Remove the fuse from fuse holder and then unscrew the mounting screws of the unit. When 

the unit is reconnected to the supply, it will need time to recharge its battery before it will be capable of a full length discharge again.

CONSTRUCTION SITES

Continuously switching on and off the mains supply to the fittings during the installation process (due to building works or for some other 

reason), could cause the fittings to discharge and charge their batteries many times over a short period which may shorten the life of the 

battery. Thomas & Betts does not recommend such practices and may not honour any warranty on the life of the batteries or the lamp 

when subjected to such harsh operating conditions. In order to prevent damage to the battery, leave the unswitched active circuit turned 

off at the circuit breaker, until the emergency lighting is required on the site.

TROUBLE SHOOTING GUIDE

If you’ve installed and connected the unit as per the instructions listed earlier and it doesn’t work properly, use the following table as a 

guide to fixing the problem. Look up the type of fault in the left column and check the possible causes from the right column.

If the unit still doesn’t work after checking these possible causes, contact Thomas & Betts Service in Australia on 1300 666 595, Monday  

to Friday, 8.30am to 4.30pm (AEST) and ask for help. Our trained service personnel will usually be able to take your call immediately and 

assist you in resolving your difficulty. Thomas & Betts is committed to providing valuable Through-Life Support for its products. 

Doc No: 29-01072

Contents

Electrical Safety Warning

Installation Instructions

Wiring Connections

Removal Method

Trouble Shooting Guide

Warranty Information (Included)

#

Fault

Possible Causes

1

Red LED not lit

(only applicable where used)

AC supply not connected; or 

AC supply turned off; or

Battery not connected; or 

Fuse missing; or

Test switch damaged

2

Red LED is lit (only applicable where used) but lamp 

doesn’t come on when test switch is pressed

Lamp damaged; or

Battery pack damaged; or

Test switch damaged

3

Lamp is lit momentarily when test switch is pressed; or

When mains fail

Battery not fully charged (allow up to 24 hours); or

Battery pack damaged

PS702M:

 12V maintained 

unit designed to be used 

remotely to provide escape 

lighting for large areas or to 

provide backup supply for the 

lighting up of difficult or hostile 

environments. The maximum 

load limit is 35W if used in a 

lift. The maximum load can be 

70W if using as backup supply 

to comply with AS/NZS2293.

Battery

PCA

Transformer

Output 

12V DC

Mains 240Vac 50Hz
For switched illumination: Connect 

incoming switched active, unswitched 

active, neutral and earth to terminal 

marked S/A, A, N and E respectively
For permanent illumination: Connect 

incoming unswitched active, neutral 

and earth to terminal marked A, N 

and E respectively

(Note: Loop link between S/A and A)

Transformer

E

S/A

N

A

Output to load max 70W 