Page 1 of 4

Installation & Operating Instructions

375LR (without test point)

376LR (with test point)

Loadbreak Elbow Connectors

CONTENTS: Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Lubricant (Do Not Substitute),

Installation/Operating Instructions.

The 375LR (without test point) and 376LR (with test point) are designed to terminate UD cable having concentric neutral and

extruded insulation shielding. The elbow provides an operating interface for connecting to an Elastimold 35kV class (21.1kV

phase---to---ground and 36.6kV phase---to---phase) 200 ampere loadbreak bushing or accessory device with fault close

rating of 10,000 amperes RMS symmetrical. When other types of UD cable are to be terminated an appropriate Elastimold

cable shield or grounding device must be used.

DANGER

All apparatus must be de--energized during installation

or removal of part(s) except for test point caps and

indicators that can be installed and operated

energized.
After installation loadbreak products can be operated

energized per operating instructions. All deadbreak

connectors must be de--energized before operating.
All apparatus must be installed and operated in

accordance with individual user, local, and national

work rules. These instructions do not attempt to

provide for every possible contingency.
Do not touch or move energized products.

“Loadbreak connectors must be operated with a full

insulated “hotstick” type live--line tool.” Consult the

company’s safe work practices for the required

live--line tool length.

Excess distortion of the assembled product may result

in its failure.
Inspect parts for damage, rating and compatibility with

mating parts.
This product should be installed only by competent

personnel trained in good safety practices involving

high voltage electrical equipment. These instructions

are not intended as a substitute for adequate training or

experience in such safety practices.
Failure to follow these instructions will result in

damage to the product and serious or fatal injury.
If this product is supplied with a protective shipping

cover(s), remove this shipping cover(s) and replace

with the appropriate HV insulated cap(s) or

connector(s) before submerging or energizing the

circuit.

FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.

IMPORTANT

1. Check contents of package to ensure they are complete

and undamaged.

2. Check all components to ensure proper fit with cable

and/or mating products.

3. Check threads by threading probe into compression lug.

If resistance is encountered prior to full assembly, check

for damage and replace damaged component.

4. Read entire installation instructions before starting.
5. Have all required tools at hand and maintain cleanliness

throughout the procedure.

Compression

Lug

Probe

Test Point

(376LR Only)

Eye

Operating

ASSEMBLED ELBOW

CAUTION:

Lubricate test point cap and assemble tightly.