background image

IS---0235

IS---151SOP

October 2000

Page 1 of 2

R

Operating Instructions

151SOP/K151SOP

Deadbreak Insulated Parking Bushing

CONTENTS: Stand Off Plug (complete with mounting hardware), Hold---down Bail Assembly, Lubricant, Operating

Instructions

The 151SOP is designed to terminate the female deadbreak connector interface of the 154LR or the 156LR Elbows (other

products should not be used since the 151SOP bail is designed to secure elbows only) rated for 15kV class (8.3kV phase---

to---ground and 14.4kV phase---to phase) 200 ampere. The K151SOP provides the same function for the 25kV class (15.2kV

phase---to---ground and 26.3kV phase---to---phase)200 ampere rating.

DANGER

All apparatus must be de--energized during installation

or removal of part(s). For loadbreak products follow

operating instructions. All deadbreak connectors must

be de--energized before operating.
All apparatus must be installed and operated in

accordance with individual user, local, and national

work rules. These instructions do not attempt to

provide for every possible contingency.
Do not touch or move energized products by hand.
Excess distortion of the assembled product may result

in its failure.
Contact with solvents, transformer oil, motor oil and

similar substances will degrade jacket conductivity

and insulation level if not immediately wiped off.

Inspect parts for damage, rating and compatibility with

mating parts.
This product should be installed only by competent

personnel trained in good safety practices involving

high voltage electrical equipment. These instructions

are not intended as a substitute for adequate training or

experience in such safety practices.
Failure to follow these instructions will result in

damage to the product and serious or fatal injury.
If this product is supplied with a protective shipping

cover(s), remove this shipping cover(s) and replace

with the appropriate HV insulated cap(s) or

connector(s) before submerging or energizing the

circuit.

FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.

IMPORTANT

1. Check contents of package to insure it is complete and

undamaged.

2. Check all components to insure proper fit with cable

and/or mating products.

3. Read entire installation instructions before starting.

4. Have all required tools at hand and observe cleanliness

throughout the procedure.

STEP 1

Remove protective shipping cap and clean the mating

interface of the insulated parking bushing. Lubricate this

surface. Use only the supplied lubricant or ELASTIMOLD

approved lubricants. DO NOT SUBSTITUTE. Other

lubricants may be harmful to this product and its mating

products. Always replace the protective cap when the

insulated parking bushing is not in use.

Clean and Lubricate

Bail

Remove Shipping Cap

IS---0235

IS---151SOP

October 2000

Printed in U.S.A.