TOP PLATE
INSTALLATION INSTRUCTIONS
FOR CONCEALED SERVICE FLOOR BOX
Catalog Number: 665-AV2
IMPORTANT:
Read all instructions before installing floor box, carpet plate or mounting kit.
TA04486 A Page 1 of 2
MINIMUM CONCRETE DEPTH FOR THE
665-AV2 FLOOR BOX IS:
4-1/2” DEEP
WARNING
ELECTRICAL HAZARD!
BE SURE POWER IS OFF!
CAUTION
FLOOR BOX SHOULD BE INSTALLED
BY A QUALIFIED ELECTRICIAN IN
ACCORDANCE WITH NATIONAL AND
LOCAL ELECTRICAL CODES.
INSTALLATION INSTRUCTIONS
(BEFORE CONCRETE POUR)
1. Remove the top of box, loosen (4) top screws and
rotate top plate away from screws. See figure 2.
2. Install (4) ground screws. See figure 3.
3. Install conduit connectors as needed.
4. Break/trim off partition from non-metallic tunnel.
Place non-metallic tunnel and partition in box.
See figure 1.
5. Install (4) leveling screws. See figure 4.
6. Replace top and tighten (4) top screws. See figure 4.
7. Adjust leveling screws so that top edge of box is
1/16” below screed line. Attach conduit and secure
box to form. See figure 4. Box is now ready for
concrete pour.
Figure 1
Figure 2
Figure 3
Figure 4
665-CST
(NOT-INCLUDED
NON-METALLIC
WIRING TUNNEL
DEVICE PANEL
(NOT INCLUDED)
665-AV2
FLOOR BOX
LOOSEN SCREWS
ROTATE PLATE
INSTALL GROUND
SCREW (4-PLACES)
(FURNISHED)
LEVELING SCREWS
(FURNISHED)
665-AV2
ASSEMBLY
PARTITION
(Save for STEP 10)