9901035-1
Page 13 of 30
400V/3ph/50Hz
if defrost electric heaters are required
230V/1ph/50Hz
if defrost electric heaters are not used
Air Curtain
Rated Electrical
Power Input (kW)
Rated Current per
phase (A)
Rated Electrical
Power Input (kW)
Rated Current (A)
VRF PHV1000 DXE HO
4.8 7.8 0.3 1.3
VRF PHV1500 DXE LO
7.8 12.7 0.35 1.8
VRF PHV1500 DXE HO
7.8 12.7 0.35 1.8
VRF PHV2000 DXE LO
9.5 15.7 0.5 2.7
VRF PHV2000 DXE HO
9.5 15.7 0.5 2.7
If the defrost electric heaters are not to be used they can be disabled by disconnecting
the neutral to the contactor coil inside the air curtain (see below and wiring diagrams on
Pages 14 & 15).
Note:
If the defrost electric heaters are disconnected, discharge air temperatures could
be very cold, approximately 6ºC. Defrost times could also be extended, particularly with
the R2-Series System. *
Do not use cable size of more than 2.5mm
2
or connection will be difficult.
See also wiring diagram on page 14 or page 15.
If the defrost electric heaters are to be disabled this can be done by disconnecting the
purple (neutral) wire from terminal A2 on the contactor inside
the air curtain. The disconnected purple wire should be
terminated safely into unused auxiliary terminal
14NO
as
shown in the adjacent picture, or into a suitable terminal block.
*NB.
Defrost does not occur with WY and WR2 systems so the
defrost cycle electric heaters should always be disconnected
on these systems.
The photo above shows the completed
wiring to terminals L1,L2, L3, N and
(Earth) for a 3 phase electrical supply
(400v/3ph/50Hz) if defrost electric
heaters are used
The photo above shows the completed
wiring to terminals L1, N and (Earth)
for a single phase electrical supply
(230v/1ph/50Hz) if defrost electric
heaters are not used