3
1.
Select appropriate grommet for specific cable
type.
3.
Cut end of cable at angle to aid in piercing
grommet. Leave additional cable for expansion
loop. See page 5 for in-line splice (two cable)
installation tips.
4.
Insert cable into expediter. If mounted on
bottom or side of pipe, punch out weep hole.
5.
Slide expediter toward pipe and route cable
through support base entry.
2.
Put together expeditor assembly. Place
grommet in support base. Snap threaded
grommet compressor into support base. Screw
support cap onto support base.
GRW-L
12 mm x 5 mm
Opening
GRW-G
9 mm x 5 mm
Opening
GRW-F
7 mm x 4 mm
Opening
Cable Type
Cable Type
Cable Type
HTEK 3C60
HTEK 3C40
HTEK 2C50
HTEK 3C50
HTEK 3C30
HTEK 2C40
TEK 3C70
HTEK 2C70
HTEK 2C30
HTEK 2C60
TEK 3C40
TEK 3C60
TEK 3C30
TEK 3C50
TEK 2C60
TEK 2C70
TEK 2C50
TEK 2C40
TEK 2C30
6.
Insert banding guide into expediter and snap
into place.
INSTALLATION PROCEDURES
9.
Cut and remove overjacket by scoring overjacket
and bending cable. Do not cut metallic braid.
8.
Cut off end of cable.
7.
Mount expediter to pipe using pipe band. Do
not band over cable.