1. 

Select appropriate grommet for specific cable 

type.

3. 

Cut  end  of  cable  at  angle  to  aid  in  piercing 

grommet. Leave additional cable for expansion 

loop. See page 5 for in-line splice (two cable) 

installation tips.

4. 

Insert  cable  into  expediter.  If  mounted  on 

bottom or side of pipe, punch out weep hole.

5. 

Slide expediter toward pipe and route cable 

through support base entry.

2. 

Put  together  expeditor  assembly.  Place 

grommet  in  support  base.  Snap  threaded 

grommet compressor into support base. Screw 

support cap onto support base.

GRW-L

12 mm x 5 mm 

Opening

GRW-G

9 mm x 5 mm 

Opening

GRW-F

7 mm x 4 mm 

Opening

Cable Type

Cable Type

Cable Type

HTEK 3C60

HTEK 3C40

HTEK 2C50

HTEK 3C50

HTEK 3C30

HTEK 2C40

TEK 3C70

HTEK 2C70

HTEK 2C30

HTEK 2C60

TEK 3C40

TEK 3C60

TEK 3C30

TEK 3C50

TEK 2C60

TEK 2C70

TEK 2C50
TEK 2C40
TEK 2C30

6. 

Insert banding guide into expediter and snap 

into place. 

INSTALLATION PROCEDURES

9. 

Cut and remove overjacket by scoring overjacket 

and bending cable. Do not cut metallic braid.

8. 

Cut off end of cable.

7. 

Mount expediter to pipe using pipe band. Do 

not band over cable.