Thermomax THX-DL User & Installation Manual Download Page 3

Temp

Control

 

|

 5 

|

 

Temp

Control

Installation

Note:

 This installation procedure is for guidance only, and its suitability should be verified by the installer.

SAFETY PRECAUTIONS

 

= WARNING! - Information which is essential for preventing hazard to personnel or device and must be read with care.

 

= DANGER! - High voltage area. Isolate power supply before any maintenance work.

The following safety precautions are strongly recommended:

1.  Before attempting to install and operate the unit, read the instruction and installation manual carefully.
2.  Installation and any maintenance should only be carried out by suitably qualified personnel.
3.  It is recommended that the unit be connected to the mains supply via a suitably rated isolating switch.
4. 

WARNING: When the unit is connected to the mains supply and the cover is open, the circuits at mains voltage will be 
exposed. 

Therefore when installing the unit, ensure all required connections (including battery connected, if included), are made and 

covers replaced before turning on the mains supply. Ensure that all the connections made are secure. If any maintenance work e.g. 
installing a new battery, is required ensure that the unit is isolated from the mains supply before removing the cover. 

Never leave the 

unit unattended if the cover has been removed and the mains supply is connected.

5.  Do not exceed unit ratings as shown on the ratings label.
6.  It is advisable to route mains cables away from low voltage or sensor cables.

(i)  THX Unit

Note:

 For viewing comfort, the unit should be positioned at eye level. The ambient temperature of the unit is (0°C to +40°C). It is always good practice to keep 

electronic equipment away from cold, heat and electrical plant, as extremes of temperature may reduce the lifetime of the device, and heavy electrical loads, 
switches, relays or contactors too close to the device may cause electrical and electro-magnetic interference when switched on or off.

(ii) Sensors

The THX may be used with a variety of sensors of different cable lengths. If required, sensors are available with extended cable lengths or 
alternatively, sensor extenders are available also in a variety of lengths. If the sensors need to be extended, but factory-made extenders are 
not available, they can be extended using a suitable 3 or 4 core cable, according to the diagram shown below

Please note however, that as with all PT100 sensor applications, a good connection is vital. It is therefore recommended that wherever there 
is any doubt, a factory extended sensor or sensor extender should be used.

(iii)  Alarm Relay

Note:

 The alarm relays are 2 contact arrangements which are isolated (volt-free).  These relays may be used to trigger an external bell, warning lamp or digital 

communicator (telephone dialler). 

Max rating of Alarm relays is 5A @ 240 VAC. 

The alarm relay is software configurable to accommodate normally open or normally closed operation, as described below.

Normally Closed Operation – This is the default mode.

Normally Open Operation – In this mode, the relay outputs will break contact (open circuit) in the event of an alarm and make contact 
(closed circuit) in the event of power failure.

If the external device is used, connect the alarm as appropriate, according to the diagram opposite.

Installation

(iv)  Power Connections and Wiring Diagram

Note:

 This device should be properly earthed. Flexible wires simplify connection to the terminals. All connections should be secure and adequately tightened. 

It is good practice to keep mains cables away from sensor cables and other low voltage signal cables.

Connect the supply to the unit, as per diagram below, using the appropriate input voltage according to the application.

(v) Battery

The battery supplied is a 3.7V Lithium-polymer rechargeable battery and is plugged in but switched OFF. This should be switched ON 
after installation. See picture below. This battery is not essential for the system operation, but is used in the case of power failure, thereby 
continuing to log the 12 sensor inputs for approximately 6 hours.

The system parameters will remain intact, in the event of a power failure, however all interface options (Ethernet, screen, keypad options, 
USB etc. will not function as normal)

It is recommended that the battery is changed every 24 months, in order to maintain good power failure backup operation. When replacing, 
ensure that the type of rechargeable battery used is as specified. 

(3.7V Lithium-polymer rechargeable battery)

WHITE
RED

BLUE

GREEN

GROUND

SENSE

COMPENSATE

Summary of Contents for THX-DL

Page 1: ...USER INSTALLATION MANUAL V3 2016 www thermomax refrigeration com THX DL Data Logger Refrigeration...

Page 2: ...sentation SUMMARY OF FEATURES Datalogger Temperature humidity from each Channel can be set to sample every 1 5 15 30 60 minutes and stored to an internal databank Up to 12 channels of data logging can...

Page 3: ...of lengths If the sensors need to be extended but factory made extenders are not available they can be extended using a suitable 3 or 4 core cable according to the diagram shown below Please note howe...

Page 4: ...tied in it It will not be possible to push the cord into the device to such an extent that it will cause a hazard Should the cord insulation fail in an anchorage that has metal parts none of the expo...

Page 5: ...so be sent in the event of loss of power from the THX DL It is the customers responsibly to keep power to the network infrastructure March 2015 3 How do I test the new Email feature Brief Set up summa...

Page 6: ...mmary Screen This screen displays the current temperature humidity readings of each of the connected channels and indicates if that channel is in alarm or not The key will return the user to the previ...

Page 7: ...daily maximum and minimum temperature which are reset at midnight 3 0 ALARM SETTINGS From the Main Screen press the key to select Alarms Settings from the main menu Confirm selection using the key to...

Page 8: ...se press key If a channel is switched off the alarm parameters will automatically revert back to the default factory settings to prevent an alarm occurrence These parameters cannot be changed until th...

Page 9: ...ain Screen press the key to select Settings from the main menu Confirm selection using the key to reveal the Settings Menu Scroll down using the key to the second page of the menu select Relay Setup f...

Page 10: ...om the main menu Confirm selection using the key to reveal the Settings Menu Scroll down using the key to the second page of the menu select Network from the menu and press the key to confirm Please e...

Page 11: ...ct the date and press the key to confirm Display the door information by selecting SHOW DOOR from the pop up menu and pressing the key to confirm View the information of any door by using the keys 6 0...

Page 12: ...m the main menu Confirm selection using the key The language used by the THX to communicate the information may be selected here i e English German or French Use the or key to select the required lang...

Page 13: ...urrently selected channel The MODULE window shows the number of the currently selected module The INPUT TYPE window shows which type of sensor is being used The CALIB DATA window shows calibration val...

Page 14: ...ey to start upload previously downloaded settings from the memory stick Do not remove the memory stick until the progress bar disappears 4 Service For use only by authorised personnel and trained inst...

Page 15: ...ontrol Web Server Web Server 1 Live Data Live data screen displays the current temperature humidity readings of each of the connected channels and indicates if that channel is in alarm or not The stat...

Page 16: ...e To change the date and time use the and click on the button to save the changes 6 Graph Graph screen allow user to generate multiple channel graph To generate the graph set the date choose the chann...

Page 17: ...t 100mm depth 180mm weight 1 4kg sensor each 0 13kg Box Material Plastic Display Large LCD with backlight SENSORS Type SX PT 100 Platinum Film Compensation 3 wire compensated Cable Length A variety of...

Page 18: ......

Page 19: ...ght to alter specifications and drawings without prior notice Issue No 3 July 2016 019264 Head Office Kingspan Environmental 180 Gilford Road Portadown Co Armagh BT63 5LF Tel 44 0 28 3836 4400 UK Sale...

Reviews: