ANWENDERHINWEISE FÜR FEUCHTEFÜHLER 

At regular environmental condition, it is recommended to calibrate the sensor annually to check the compliance with the accuracy 

required in the application. The following conditions can damage the sensor element or lead in long therm to loss of the specified 

accuracy:  

 

Mechanical stress 

 

Contamination (e.g. dust / fingerprints) 

 

Aggressive chemicals 

 

Ambient conditions (e.g. condensation on measuring element) 

 

Do not touch the sensor 

elements! 

Re-calibration or exchange of the sensor element are not subject of the general warranty. 

» 

TECHNICAL DATA 

Measuring values 

Humidity, temperature, conductivity 

Output switch contact 

NO contact, max. 250 V / 3,0 A (resistive, floating) 

Power supply 

15..24 V = (±10%) or 24 V ~ (±10%) SELV 

Power consumption 

max. 2,3 W (24 V =) | max. 4,3 VA (24 V ~) 

Output signal range temp 

(Scaling analog output)

 

0..+50 °C (default setting), optionally configurable via Thermokon USEapp 

Measuring range humidity 

0..100% rH non-condensing 

Accuracy temperature 

±0,5 K (typ. at 21 °C, within default measuring range) 

Accuracy humidity 

±2% between 10..90% rH (typ. at 21 °C) 

Display 

LED green – power supply OK; LED red – condensation 

Enclosure 

enclosure USE-L, PC, pure white, cover PC, transparent, with removable cable entry 

Protection 

IP65 according to EN 60529 

Cable entry 

Flextherm M20 for wire Ø=4,5..9 mm incl. seal insert for double cable entry for wire max Ø=6 mm and M25, for 

wire max. Ø=7 mm, seal insert 

Connection electrical 

removable plug-in terminal, max. 2,5 mm², sensor wire white 2 m (default), for other lengths please request 

Ambient condition 

0..+50 °C, max. 85% rH short term condensation 

Delivery content 

1x syringe with terminal contact fluid, incl. mounting base enclosure USE-L pure white 

Configuration 

Thermokon USEapp, LoRaWAN® Downlink, Jumper 

Notes 

other cable lengths on request 

» 

LoRaWAN® 

Radio technology 

LoRaWAN

®

 

LoRaWAN version 

1.0.2 

Device class 

Class A 

Frequency 

EU868 (863-870 MHz) 

Max. transmission power 

+14 dBm (25 mW) 

Receiver sensitivity 

-137 dBm 

Antenna 

Internal send- / receiver antenna, external antenna available on request 

LoRaWAN Features 

Over the Air Activation (OTAA), Adaptive Data Rate (ADR) 

Data transmission 

(configurable) 

Configurable transmission interval, factory default value 5 min 

 

» 

INFORMATION ABOUT LORAWAN SPECIFICATION 

 

The Thermokon LoRaWAN specification can be downloaded from our website. 

 

 