Thermokon STC-DO8 Datasheet Download Page 1

 

 

» STC-DO 8 Type 3

 

 

  Wireless Actuator with 8 digital outputs 

 

 

 

 

 

Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany  tel: +49 2778 6960-0  fax: -400  

www.thermokon.com

  

[email protected]

 

 

STC-DO8_Typ3_EasySens_Datasheet_en.docx   © 2021 

Datasheet

 

Subject to technical alteration 

Issue date: 12.01.2021 • A112 

 

 

 

 

 

» 

APPLICATION 

Bidirectional receiver with 8 digital outputs (or 12 with extension module STC-Plus 4DO). For heating/cooling control, fan coil control, control of 

lights and blinds etc. Incl. ext. receiving antenna (2,5 m).  

» 

TYPES AVAILABLE – TYPE 3 

Wireless receiver – multi relay 24 V 

STC-DO8 24 V type switch actuator 

Wireless receiver – multi relay 100..230 V 

STC-DO8 230 V type switch actuator 

» 

SECURITY ADVICE – CAUTION 

The installation and assembly of electrical equipment should only be performed by authorized personnel. 
The product should only be used for the intended application. Unauthorised modifications are prohibited! The product must not be 

used in relation with any equipment that in case of a failure may threaten, directly or indirectly, human health or life or result in 

danger to human beings, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating 

equipment.  
Please comply with 

 

Local laws, health & safety regulations, technical standards and regulations 

 

Condition of the device at the time of installation, to ensure safe installation 

 

This data sheet and installation manual 

» 

NOTES ON DISPOSAL 

As a component of a large-scale fixed installation, Thermokon products are intended to be used permanently as part of a building 

or a structure at a pre-defined and dedicated location, hence the Waste Electrical and Electronic Act (WEEE) is not applicable. 

However, most of the products may contain valuable materials that should be recycled and not disposed of as domestic waste. 

Please note the relevant regulations for local disposal. 

 

 

517690

 

Summary of Contents for STC-DO8

Page 1: ...used for the intended application Unauthorised modifications are prohibited The product must not be used in relation with any equipment that in case of a failure may threaten directly or indirectly h...

Page 2: ...smit receive antenna Data transmission bidirectional Power supply STC DO8 24 V 18 24 V SELV STC DO8 100 230 V 100 240 V 10 Power consumption STC DO8 24 V typ 2 0 W 24 V 3 5 VA 24 V STC DO8 100 230 V 3...

Page 3: ...us it is also possible to learn in and to evaluate sensors which s profiles are not supported by the STC DO8 actually see page 7 individual sensor EEP EnOcean Equipment Profiles Device D5 00 01 single...

Page 4: ...ly downwards and should have a minimum distance of approx 90 mm to the wall The distance to other senders e g GSM DECT Wireless LAN EnOcean senders should be 2 m at least To match the colour of the ro...

Page 5: ...ortechnik GmbH Platanenweg 1 35756 Mittenaar Germany tel 49 2778 6960 0 fax 400 www thermokon com email thermokon com STC DO8_Typ3_EasySens_Datasheet_en docx 2021 Control of 4 lamps and 2 blind shutte...

Page 6: ...ugh the button is released again lock Shutter function The output Up Down is switched on for the period of the adjustable after run time if the button Up Down is pushed lock If the corresponding butto...

Page 7: ...up time Function 1 Button Operation If a learned in button is pushed the output is switched on and automatically switched off again after expiration of the after run time If the after run time is dea...

Page 8: ...the lower threshold the output is switched off Function 1 Operation of buttons If the measuring value of the data byte selected exceeds the upper threshold the output is switched on for the period of...

Page 9: ...lower threshold to analyse the individualsensor Adjustable range 0 255 Factory setting 85 Upper Threshold Setting of the upper threshold to analyse the individualsensor Adjustable range 0 255 Factory...

Page 10: ...o working correctly after a power failure the STC DO8 has an integrated energy buffer supplying the internal clock automatically for 24 hours Time switch 1 8 time Time setting for the corresponding ti...

Page 11: ...umination period Adjustable range 1 60 minutes Resolution 1 minutes Factory setting 15 minutes Function of Output 8 Instead of a standard switching output output 8 can also be used for an OR function...

Page 12: ...ns F1 and F2 of the switched on STC DO8 for 10 seconds until a tone of confirmation is heard The unlocking is done in the same way Restart The STC DO8 can be restarted in the menu General Restart To r...

Page 13: ...ain number of outputs The extension module is identified automatically by the STC DO8 when starting the device The identification is displayed with a corresponding message Besides the common menus out...