background image

TK-335034-Rev01_070223.pdf

GB - 1

Thermokon Sensortechnik GmbH • www.thermokon.de • [email protected]

1.  Description

The radio actuator controls roller shutters and blinds with
limit switches (230V/50 Hz motors) with the output UP 

K

 and

the output DOWN 

L

.

The radio actuator is controlled by radio signals from radio
sensors. Each radio sensor can simultaneously control an
unlimited number of radio actuators.
The radio sensors have a fixed address and must be assigned
on a radio actuator (max. 32 radio sensors). The memory of
each radio actuator is empty when delivered.

Function 1

 (standard function) is preset by default in the

radio actuator of a freshly assigned radio sensor.
The radio actuator’s function can be changed by programming
to respond to any assigned radio sensor (see Point 6).

2.  Mounting

Mounting and set-up may only be carried out by an authorised
professional. All works may only be performed once the
mains power supply 230V/50Hz~ has been switched off.
Mounting must adhere to the valid laws, standards and
regulations. The supply line may only be fused with a fuse
or circuit breaker (max. 10A).

For programming, the radio actuator must be connected to
the mains power supply. The programming is retained even
in a power failure.

NEVER mount the radio sensor or radio actuator in a metal
housing or directly next to large metal objects.
It is also not advisable to mount the radio actuators on the
floor or close to the floor.

The following points must be observed:

- the valid laws, standards and regulations
- the best available technology at the time of installation.
- the operating instructions of the Thermokon radio products.
- the fact that operating instructions can only contain general

guidelines and that these must be considered in the context
of a specific system.

Caution!!

 The Thermokon radio products must 

not

 be used

with devices, which could affect human health or safety, or
endanger humans, animals or material assets.

3.  Technical data

Installation and operating instructions

Radio actuator SRC-DO jalousie 230V for
radio sensors with Enocean technology

Art.no.:

 

335034

GB

Radio sensor assigned

(LED on)

radio actuator function 1

Radio sensor deleted

(LED off)

Assign/delete radio sensor

Press a button of the
radio sensor 

once

4.  Assigning or deleting radio sensors

Radio sensors can be assigned or deleted in the 

learn

mode

 of the radio actuator. Learn mode is activated by

pressing the 

LRN/SET button

 (LED flashes red).

If a button of the radio sensor that 

is to be assigned

 is

pressed 

once

 in learn mode and recognized by the radio

actuator (

LED on

), the radio sensor 

has been assigned

.

If a button of an 

already assigned

 radio sensor is pressed

once

 and recognized by the radio actuator (

LED off

), the

radio sensor 

has been deleted

.

Caution!!

 

If the button off a radio sensor is pressed repeatedly

the radio sensor will be alternately assigned or deleted!

After a radio sensor has been assigned or deleted the radio
actuator returns to learn mode (LED flashes red) and other
radio sensors can be assigned or deleted. When no button
of a radio sensor is pressed, the radio actuator leaves the
learn mode after approx. 30s independently.

Press the 

LRN/SET

button briefly

Learn mode

(LED flashes red)

Press the 

LRN/SET

button briefly

Learn mode OFF

(LED off)

Function 1

 (standard function) is preset by default in the

radio actuator of a freshly assigned radio sensor.
If desired, the radio actuator’s function and its parameter
can be changed by function programming (see Point 6) for
each 

assigned radio sensor

.

s. Point 4

5.  Deleting all assigned radio sensors

Press the 

CLR/MODE

 

button

 and hold it down for approx.

2s. During this time, the memory is completely deleted
(delivery status).
Then, the radio actuator is in learn mode (LED flashes red).

Press the 

CLR/MODE

button for longer

All assigned
radio sensors deleted

Learn mode

(LED flashes red)

230V~

50Hz

9 mm

N N

L

L  max.600VA

CLR/MODE-button
Parameter setting

LRN/SET-button
with LED
Learn mode and

Function
programming

Learn mode

:

LED = red
Function programming:
LED = green oder orange

N  N     L

N  

N

L

M

u

u

Transmission frequency 

868.3 MHz 

Power supply

 

230 V~ / 50 Hz

 

Fusing the supply lines

 

Circuit breaker or fuse  
(max. 10 A)

 

Max. switching capacity

 

600 VA

 

Ambient temperature

 

-20° to +40

q

C

 

Storage temperature

 

-40° to +85°C

 

Test specifications

 

EN 60669-2-1

 

Certifications

 

CE

 

Protection level

 

IP 20

 

6.  Function programming

The radio actuator’s 

function 

and its 

parameter 

can be

changed by function programming each 

assigned radio

sensor

 (see Point 4).

Function programming is activated by pressing an holding the

LRN/SET

 button until confirmed (LEDs flash green rapidly).

Function programming can be manually terminated by
activating the 

CLR/MODE

 button. Without activating the

button on a radio sensor, the radio actuator will terminate
function programming automatically after about 30s.

If function programming is active, a button of the radio
sensor must be pressed for recognition, for which the function
of the radio actuator is to be changed.
Once the radio sensor is recognized by the radio actuator, the
radio actuator is active (LED flashes orange).
The number of times the LED flashes corresponds to the
radio actuator’s current function. This function can then be
changed by the number of times that the 

LRN/SET

 button is

activated (e.g. pressing 

LRN/SET twice

 = Function 2).

The parameter setting is accessed in function programming
by activating the 

CLR/MODE

 button. Subsequently the

radio actuator is active (LED flashes green).
Parameter setting can be manually terminated by activating
the 

CLR/MODE

 button.

The number of times the LED flashes corresponds to the
parameter currently set for the radio actuator’s current
function. This parameter can then be changed by the number
of times that the 

LRN/SET

 button is activated

(e.g. pressing 

LRN/SET twice

 = Parameter 2).

Recognition of radio sensor

Press a button of the radio sensor

Idle state

(LED off)

Press the 

CLR/MODE

button briefly

Press the 

LRN/SET

button for longer

Function programming

 (LEDs flash green rapidly)

Radio actuator is active

(LED flashes orange)
number of flashing = function

Press the 

LRN/SET

 button to

select the function 1-7

number of actuations = function!

Press the 

CLR/MODE

button briefly

Parameter setting

Radio actuator is active

(LED flashes green)
number of flashing = parameter

Press the 

LRN/SET

 button to

select the parameter

number of actuations = parameter!