Manual NOVOS und thanos EVO
Seite
22
Thermokon Sensortechnik GmbH
5.2
Data block “Room Climate”
Parameter
Description
N3
N5
N7
Touch/
EVO
Min
Max
Default
Access
Data
address
Room Occupancy
Switching the room occupancy
N7/Touch/EVO: Toggle-
Function in
the device menu
0 = Unoccupied
1 = Occupied
●
●
●
●
0
1
Reset
value
Addr.
1307
r / w
uint16_t
100
ECO Mode
Switching the ECO Mode
0 = ECO not active
1 = ECO active
●
●
0
1
0
r / w
uint16_t
101
Colour ECO function
Colour of the ECO icon in the status
bar
0 = transparent (Icon not visible)
1 = white
2 = black
3= red
4 = green
5 = blue
6 = yellow
7 = magenta
8 = turquoise
9 = orange
10 = Contrast colour
●
●
0
10
4
r / w
uint16_t
102
Setpoint (effective)
Setpoint set by the user on the
device. The value can be overwritten
by the BMS at any time.
210 = 21,0 °C
●
●
●
●
min
max
Base
Setpoint
r / w
int16_t
103
Fan stage (internal)
Fan stage set by the user
0 = OFF
1 = Stage 1
2 = Stage 2
3 = Stage 3
4 = Stage 4
5 = Stage 5
6 = Auto
●
●
●
0
6
Reset
value
(N7 /
Touch /
EVO)
r
uint16_t
104
Fan stage (Feedback from
BMS)
Overwriting the fan stage
If the operator has selected the Auto
Fan Mode (104=6), the exact fan
level can be additionally displayed
with the higher-level control.
Exception:
With NOVOS 7, only the
designation AUTO is displayed for
parameter 7-12 in the fan menu.
Attention:
With NOVOS 5, only the
AutoStages(6..12) can be
overwritten
0 = OFF
1 = Stage 1
2 = Stage 2
3 = Stage 3
4 = Stage 4
5 = Stage 5
6 = Auto
7 = Auto Stage 0
8 = Auto Stage 1
9 = Auto Stage 2
10 = Auto Stage 3
11 = Auto Stage 4
12 = Auto Stage 5
◌
only 6
to 12
◌
●
0
12
Reset
value
(N7 /
Touch /
EVO)
w
uint16_t
105
Overwrite temperature value
on home screen
The temperature value displayed on
the home screen can be
overwritten/preset via the BMS.
-1 = Internal Temperature value
Range temperature writable
0…500 = 0…50,0 °C
0…1220 = 0…122,0 °F
●
●
-1
1220
-1
r / w
int16_t
106