CONFIGURATION AND COMMISIONING
DIP 1 – WakeUp cycle / Heartbeat
The "WakeUp" time defines the interval in which the device
"wakes up" and sends a telegram if necessary (see technical
data). With every 10th WakeUp a telegram is definitely
generated.
1
Factory default: off
on
240 Sek. Wakeup / Heartbeat x10
off
100 Sek. Wakeup / Heartbeat x10
DIP 2 – EnOcean Security
Encrypted data transmission protects against various types of
attack, such as repeat and eavesdropping attacks or fake
telegrams.
2
Factory default: off
on
Encryption mechanism enabled
off
Encryption mechanism disabled
DIP 3 – Check sum
By default, the radio transmitter uses the checksum CRC8 in
the transmitted telegrams. This has the advantage that faulty
telegrams are better verified and sorted out in critical radio
links. Radio receivers older than the TCM3xx only support
simple checksum. In this case the radio transmitter must be
changed to simple checksum. To do this, the learn button must
be pressed 5 times in succession. The simple checksum is
compatible with all receivers. If you want to change the
transmitter back to CRC8 checksum, press the learn button
three times in succession.
3
Factory default: off
on
Simple Check sum
off
CRC8
DIP 4 – Energy status message
If the energy state is low, an additional signal telegram (SIG) -
[06 01] is sent every 2nd transmission interval. Ensure
sufficient ambient brightness, change the battery or insert a
battery for support due to insufficient ambient brightness.
4
Factory default: off
on
Activated
off
Disabled
DIP 5 – reserved
4
on
off
Battery AA
(optional)
Learn button