ProReact EN Analogue Cable Test Kit Instructions

Document Ref.  PACC-CTK

Operating Instructions contd.

6.   It may be preferable to temporarily secure the heating cable to the sensor cable using the provided tie wraps. Alternatively, it is 

acceptable to temporarily attach the heating cable to the support brackets.

7.   Once the heating cable has been fixed in place and the pipe insulation placed around the sensor cable and heating cable, plug the 

heating cable into the power supply unit on the front panel (see Figure 3). The heating cable plug pushes into the socket and then 
twists clockwise to lock in place. To remove the heating cable pull the silver lever back on the plug and twist anti-clockwise.

8.  

Before plugging the power supply unit into a suitable mains outlet, check the supply voltage switch on the rear panel of the 
power supply unit is set to the appropriate voltage (either 240Vac or 120Vac)

. The supply voltage switch is set to 240Vac by 

default. Use a flat screwdriver to turn the supply voltage switch to the correct setting. The power supply unit may be damaged if 
the supply voltage switch is set incorrectly.

9.   Plug the power supply unit into a mains supply, able to supply a minimum of 3A, using the supplied lead. If a different mains outlet 

plug is required it may be sourced locally and connected into the power supply unit 3-pin C14 IEC socket on the rear panel.

10.  Once the power supply unit has been plugged in it should power up and the red Stop button will be lit.

11.   Ensure the heating cable is installed correctly. Any section of heating cable not installed around the sensor cable should be left in 

open air and must not be covered up or overlap with other sections of the heating cable, which may result in overheating.

12.   Where possible, it will aid testing of the ProReact EN Analogue system to reduce the chosen alarm temperature to the lowest 

setting for the purpose of the test. For example, if the current alarm temperature setting is 100 deg C, for the duration of the 
test the alarm temperature setting should be changed to 64 deg C or 54 deg C. The minimum alarm temperature setting will 
depend upon the present ambient temperature of the sensor cable, a higher ambient temperature will necessitate a higher alarm 
temperature. Refer to the ProReact EN Analogue installation and instruction manual for guidance. If the alarm temperature setting 
was changed always return the setting to the original value once the test is completed.

13.   Press the green Start button on the front panel of the power supply unit to start the test. The green Start button will light up 

and the red Stop button light will turn off. The power supply unit supplies power to the heating cable for approximately 20 
minutes, during which time the temperature around the sensor cable where the heating cable has been installed should increase 
sufficiently enough to trigger an alarm. 

14.   After the green Start button has been pressed, check the ammeter on the power supply unit front panel to ensure the heating 

cable is receiving power.

 

1.  For the ProMinder Red cable the ammeter should show approximately 1A

 

2.  For the ProMinder Blue cable the ammeter should show approximately 3A

 

3.  For the ProMinder Brown cable the ammeter should show approximately 4.9A

 

If the ammeter does not show the correct value, press the red Stop button immediately and investigate why the current may  

 

be incorrect (see troubleshooting section).

15.   No further action needs to be taken with the power supply unit during the test. It may be helpful to monitor the current sensor 

cable resistance on the analogue control unit under test to check the resistance is decreasing as the test progresses (see the 
ProReact EN Analogue installation and instruction manual for reading the current sensor cable resistance).

16.   An alarm should be triggered on the ProReact control unit before the 20 minute test period is over. The heating cable heats up 

slowly to prevent overheating and requires a minimum of 5 minutes to reach a temperature required to trigger an alarm. It may be 
necessary in some installations and test setup to wait for the entire test period before an alarm is triggered. Monitor the control 
unit resistance to determine if and when an alarm is going to be triggered.

17.   After 20 minutes the power supply unit will automatically switch off the heating cable, the red Stop button light will turn on and 

the green Start button light will turn off. The heating cable can take up-to 20 minutes to cool down before a test can be repeated. It 
is strongly advised not to immediately restart a test as this may result in the sensor cable or heating cable being damaged.

18.   After a successful test the heating cable and pipe insulation should be carefully removed from the sensor cable section and the 

sensor cable checked for any signs of damage or overheating.

Summary of Contents for ProReact EN Analogue

Page 1: ... www thermocable com Linear Detection Technology Made Simple Page 1 of 8 Revision 1 0 Mar 2020 ProReactENAnalogueCableTestKitInstructions DocumentRef PACC CTK ProReactENAnalogue LinearHeatDetection SensorCableTestingInstructions ...

Page 2: ...ar 2020 ProReactENAnalogueCableTestKitInstructions DocumentRef PACC CTK Contents ProReact EN Analogue Sensor Cable Test Kit Page 3 Overview Kit Contents Technical Information Operating Instructions Page 6 Troubleshooting Page 8 ...

Page 3: ...have been made accessible during the system design and installation as per the manufacturer s recommendations A functional test is straightforward to be undertaken and a test kit can be re used where necessary Kit Contents Each ProReact EN Analogue Sensor Cable Test Kit A1900 contains Part Code Product Description Quantity Spare part availability A1904 120V 240Vac to 50Vac Power supply unit 1 3 A1...

Page 4: ...chnicalInformation 120V 240Vacto50VdcPowersupplyunit Part No A1904 Part Description 120V 240Vac to 50Vac power supply unit Dimensions inc handle 185mm H x 160mm W x 260mm D Operating Temperature 0 C to 50 C Operating Humidity 0 to 90 RH Input Voltage 120V or 240Vac switchable Output Voltage 50Vac Max Input Current 1 5A Max Output Current 5A Figure 1 Power supply unit rear ...

Page 5: ...ture 40 C to 40 C Operating Humidity 0 to 99 RH Thermal Power Output Approx 15W m Part code Part Description Heated Length m A1901 ProMinder Red Cable for zone lengths between 50m 125m 3 6 A1902 ProMinder Blue Cable for zone lengths between 100 350m 10 2 A1903 ProMinder Brown Cable for zone lengths between 175m 500m 16 6 each cable includes 5m cold lead with plug on for connecting to power supply ...

Page 6: ...select ProMinder Brown cable 3 Locate a suitable section of sensor cable to attach the heating cable to A minimum of 1 of the sensor cable will need to be heated but for the best test results try and attach the heating cable to approximately 3 of the sensor cable For example if the zone length is 88m as previously calculated attach the ProMinder Red cable to 2 6m 3 of 88 metres section of sensor c...

Page 7: ... and instruction manual for guidance If the alarm temperature setting was changed always return the setting to the original value once the test is completed 13 Press the green Start button on the front panel of the power supply unit to start the test The green Start button will light up and the red Stop button light will turn off The power supply unit supplies power to the heating cable for approx...

Page 8: ...r does not move after the green button is pressed check the cable is attached correctly to the power supply unit Disconnect power to the power supply unit and check the fuse on the front panel see Figure 3 The fuse can be removed by twisting the fuse plug anti clockwise If the power supply unit red Stop button does not light up after connecting the unit to a mains supply Check the fuse on the main...

Reviews: