Thermo Fisher Scientific
AutoPILOT PRO Flow Computer User Guide 6-11
Figure 6–9. SIB to main board wiring, ATEX/Brazilian installations
4.
TB1 and TB3 on the SIB are used for connection to the AutoMITTER
PRO transmitter wiring diagram. Note the I.S. parameters for each
separate channel from TB3:
Uo = 7.14 V
Io = 2.404 A transient
Po = 0.92 W
Io = 136 mA continuous
Ci = 0
Li = 0
Co = 240
µ
F
Lo = 24.6
µ
H
Lo/Ro = 33
µ
H/ohm
5.
J38 on the main board is for SIB / Comm3 selection. Install a jumper
to select SIB.
6.
Return the main board and mounting bracket to the down position,
tighten the thumbscrews, and shut the enclosure door.