Section 3 – SR-2 Software Description
FreshSet Floor Limit
Micro Rev
All
HMI Rev
All
Choices
1.0°F (0.5°C) to 6.0°F (3.5°C)
Factory Set
2.5°F (1.4°C)
Exceptions
Only appears if Controlling Sensor =
Return.
Description
This feature allows the minimum
discharge air temperature during return air
modulation to be programmed. When the discharge
air temperature reaches this number of degrees
below setpoint, control is switched to the discharge
air sensor. The discharge air temperature is limited
to the programmed limit to provide additional
protection from freezing for sensitive loads. Control
will switch back to the return air sensor when the
return air temperature reaches setpoint.
For example, with a 35°F (1.7°C) setpoint and a
2.5°F (1.4°C) Floor Limit, the discharge air
temperature is limited to 32.5°F (0.3°C).
The minimum discharge air temperature is controlled
to 29°F (-1.5°C) regardless of the programmed floor
limit with setpoints of 30°F
(-1.1°C) and higher.
FreshSet Freeze Protection
Revision
All
Revision
All
Choices
Off or On
Factory Set
Off
Exceptions
Only appears if Controlling Sensor =
Return.
Description
Freeze protection controls the
discharge air temperature to 35
°
F (2°C), minus the
limit determined by the setting of FreshSet Floor
Limit.
Freeze Protection is a subset of return air
modulation control. The mode is designed to allow
the unit to pull the return air temperature to setpoint
while preventing freeze damage. It is designed for
use with medium to high setpoints and high
refrigeration loads or lightly insulated trailers. This
feature is active for setpoints above 35°F (1.7°C).
Example: Setpoint is 49°F (9°C). Floor Limit is 4°F
(3.3°C). The minimum discharge air temperature
with Freeze Protection on is 31°F, determined by
(35°F-4°F). In Celsius the minimum discharge air
temperature is -0.5°C, determined by
(1.7°C – 1.2°C).
Freeze Protection is not available for OptiSet ranges
where the maximum setpoint temperature is less
than 35
°
F (1.7°C).
3-38
31 January 2005
Summary of Contents for SR-2 SmartReefer2
Page 4: ......
Page 7: ...Tab goes here and the next page should be GREEN Section 1 Safety...
Page 8: ......
Page 10: ...Section 1 SR 2 Safety Information 1 2 18 January 2005...
Page 14: ...Section 1 SR 2 Safety Information 1 6 18 January 2005...
Page 15: ...Tab goes here and the next page should be GREEN Section 2 Hardware Description...
Page 16: ......
Page 48: ...Section 2 SR 2 Hardware Description 2 32 31 January 2005...
Page 49: ...Tab goes here and the next 2 pages should be GREEN Section 3 Software Description...
Page 50: ......
Page 96: ...Section 3 SR 2 Software Description 3 46 31 January 2005...
Page 97: ...Tab goes here and the next page should be GREEN Section 4 Operation...
Page 98: ......
Page 181: ...Tab goes here and the next 2 pages should be GREEN Section 5 Diagnostics...
Page 182: ......
Page 266: ...Section 5 SR 2 Diagnostics 5 84 02 February 2005...
Page 267: ...Tab goes here and the next page should be GREEN Section 6 Service Procedures...
Page 268: ......
Page 270: ...Section 6 SR 2 Service Procedure Index Page 2 01 February 2005...
Page 282: ...Section 6 SR 2 Service Procedure A01B Page 6 P41RA01B 31 January 2005...
Page 298: ...Section 6 SR 2 Service Procedure A02A Page 12 P41RA02A 02 February 2005...
Page 318: ...Section 6 SR 2 Service Procedure A03B Page 4 P41RA03B 30 January 2005...
Page 338: ...Section 6 SR 2 Service Procedure A15A Page 4 P41RA15A 30 January 2005...
Page 360: ...Section 6 SR 2 Service Procedure A46B Page 8 P41RA46B 30 January 2005...
Page 366: ...Section 6 SR 2 Service Procedure A48A Page 6 P41RA48A 30 January 2005...
Page 376: ...Section 6 SR 2 Service Procedure A50A Page 6 P41RA50A 31 January 2005...
Page 394: ...Section 6 SR 2 Service Procedure F08A Page 4 P41RF08A 30 January 2005...
Page 398: ...Section 6 SR 2 Service Procedure F09A Page 4 P41RF09A 30 January 2005...
Page 402: ...Section 6 SR 2 Service Procedure G03A Page 4 P41RG03A 31 January 2005...
Page 406: ...Section 6 SR 2 Service Procedure H04A Page 4 P41RH04A 30 January 2005...
Page 407: ...Tab goes here and the next page should be GREEN Section 7 Service Information...
Page 408: ......
Page 410: ...Section 7 SR 2 Information 7 2 02 February 2005...
Page 419: ...Tab goes here and the next page should be GREEN Section 8 Schematics and Wiring Diagrams...
Page 420: ......
Page 422: ...Section 8 SR 2 Drawings 8 2 01 February 2005...
Page 424: ...Section 8 SR 2 Drawings 8 4 01 February 2005...
Page 425: ...8 5...
Page 426: ...8 6...
Page 427: ...8 7...
Page 428: ...8 8...
Page 429: ...8 9...
Page 430: ...8 10...
Page 431: ...8 11...