7
A) GENERAL
The installation of the unit shall be in accordance with state and local regulations.
B) FREIGHT CLAIMS
All units should be inspected for damage upon arrival. Concealed damage claims should be filed
immediately against the carrier by the consignor. The carrier is responsible for taking prompt
action on all claims.
C) SIZING
Replacement boilers should not be sized from the firing rate of the old boiler; a DOE sponsored
study indicated 65% of the heating units in U.S. homes are substantially oversized. A complete
heat loss calculation of the structure is necessary to choose the proper size unit to install. The boil-
er should be sized to within 25% of the actual calculated heat loss of the structure. Over sizing
will result in short cycling and inefficient operation.
D) BOILER LOCATION
1.
Boiler to be installed in a level position with clearances in accordance with NFPA 31 Table
10.6.1.
STANDARD CLEARANCES
Front 24"
Sides 6"
Top 18"
Rear 12"
Chimney Connector 18"
Floor: Sizes 90-150 may be installed on combustible flooring
2.
Reduced clearance installations shall comply with NFPA 31 Table 10.6.2.
3.
To move the unit, push against the flue box or skids. Pushing or pulling the jacket or burner
will result in damage.
4.
Be sure to level the unit by inserting shims under the elevated base.
E) AIR FOR COMBUSTION AND VENTILATION - CHIMNEY VENT APPLICATIONS
The unit must be installed where provisions exist for combustion and ventilation air. Ordinarily,
provisions may be furnished by the following methods.
Installation/Qualified Heating Contractor Only