13
ENGLISH
GENERAL INFORMATION
GENERAL INFORMATION
IMPORTANT NOTES FOR BURNER INSTALLATION
Before fixing the burner to the boiler, make sure that:
- The door opens the right way (see the relevant sections
for details on how to reverse the door)
- The length (L) of the burner fixing bolts is less than
(S), i.e. the total depth of the seal, plates and washer.
Longer bolts can cause the door to warp, compromising
its ability to seal the boiler hermetically and permitting the
release of combustion fumes.
To ensure correct burner installation, also refer to the burner’s
own manual.
L < S
S
L
If you are installing a new boiler but re-using an old burner,
always perform the following checks:
- Make sure that the performance of the old burner is ad-
equate for the requirements of the boiler
- Make sure that the length and diameter of the burner
nozzle are as specified in the following table.
b
When you finish installing the burner in the boiler, fill the
gap between the burner’s blast tube and the refractory
material in the door with the ceramic insulation (A) sup-
plied with the boiler.
A
Ø
L
THC GREY
150
210
270
350
450
Burner head
L min. (mm)
110
170
180
180
195
Hole in door
Ø (mm)
162
162
180
180
210
THC GREY
600
800 1000 1250 1450
Burner head
L min. (mm)
200
200
200
200
205
Hole in door
Ø (mm)
210
235
235
230
265
a
Do not re-use old burners if their blast tube lengths are
below those specified in the table.
Identification
The products are identified by:
Serial number plate
This is located on the boiler body and specifies the serial num-
ber, model, and furnace power.
Data plate
This lists the technical specifications and performance of the
product. It comes inside the documentation envelope. On
completion of the installation you MUST apply it in a clearly
visible position at the top of one of the side panels. If you dam-
age or lose this label, order a replacement immediately from
T
's Technical Assistance Centre.
b
If these plates or any other means of clearly identifying
the product are defaced, removed or lost, proper instal-
lation and servicing may be rendered difficult.
23
27
0000581
WEEK OF
MANUFACTURE
Matricola
Modello
bar
kW
Pressione massima
di esercizio
PMS
Portata Termica
nominale
Qn (Hi)
Combustibile Utilizzato
Codice
PIN
Portata
Termica
Pressione
massima
COLLEGAMENTO DI TERRA OBBLIGATORIO
Combustibile Utilizzato
Matricola
Codice
kW
mbar
bar
CALDAIA A CONDENSAZIONE
°C
kW
Contenuto
acqua
Categoria dell' Apparecchio
Pressione
focolare
Tipo di Apparecchio
Anno
Paese di destinazione
Modello
PMS
Qmax(Hi)
di
esercizio
Tipo
Potenza
Utile
Pn
max
40/30°
Tmax
Temp.
massima
ammessa
I
Portata
Termica
kW
Qmin(Hi)
Potenza
utile
kW
Pn
max(Hi)
Potenza
utile
kW
Pn
min(Hi)
067637IT
067637IT
RIELLO S.p.A. Via Ing. Pilade Riello, 7 - 37045 Legnago (VR)
RIELLO S.p.A. Via Ing. Pilade Riello, 7 - 37045 Legnago (VR)
Summary of Contents for THC 1000 GREY
Page 1: ...THC 150 1450 GREY INSTALLATION OPERATION AND MAINTENANCE MANUAL ...
Page 37: ...37 ENGLISH TECHNICAL ASSISTANCE CENTRE TECHNICAL ASSISTANCE CENTRE ...
Page 38: ...38 ENGLISH TECHNICAL ASSISTANCE CENTRE TECHNICAL ASSISTANCE CENTRE ...
Page 39: ...39 ENGLISH TECHNICAL ASSISTANCE CENTRE TECHNICAL ASSISTANCE CENTRE ...