INSTALLATION

INSTALLATION

UNPACKING THE PRODUCT

Heaters 

T

 

TBSS

 are supplied in a single package 

on a wooden pallet.

The insulation and the lining components of the models 800 

and 1000 are supplied separately from the structural work and 

are to be assembled upon receiving the product as described 

in the paragraph "Assembly of the insulation and the lining 

(models 800 - 1000)". For these models the magnesium anode 

is supplied in a cardboard box.

The following items are delivered in a plastic bag inside the 

packaging:

- Instruction manual

- Bar code label

- Hydraulic test certificate

- Energy label (to be applied to device upon installation)

- No. 4 adjustable feet to be mounted during installation 

(for models 800-1000 only).

The instruction manual is an integral part of the solar stor-

age cylinder. Once located, read it thoroughly and keep 

it safe.

For handling operations, thoroughly follow the instruc-

tions on device package label.

ASSEMBLY OF THE INSULATION AND 

THE LINING (MODELS 800 - 1000)

The assembly of the insulation and lining components must 

be performed at the site of installation to facilitate passage 

through any doors and/or entries to the room.

4

5

2

1

7

3

3

1

6

1

3

L

3

L

Proceed as follows:

- Fit the magnesium anode (6) with its seal in the sleeve 

and fix it in place

- Assemble the insulating covers (1) around the body of 

the heater, making sure that the engagement points on 

the edges are positioned correctly. The edges are not 

required to be closed completely

- Place the front protection plate (3) correctly on the at-

tachments

- Place the washers on the attachments and the protec-

tion for the inspection flange (4)

- Place the rear protection plate by closing the interlock-

ing flaps (L) without closing completely (leave one tooth 

open)

- Apply the upper insulation (2) and the upper cover (5) 

(in order to insert the cover, exert a light and homoge-

neous pressure)

- Close the interlocking flaps (L) completely, which were 

previously left with an open tooth

- Fit the cover of the inspection flange using the two 

self-tapping screws (7) provided

- Apply the technical data plate and serial number plate.

If disassembling is required, proceed in reverse order.

Wear suitable personal protective equipment and use 

suitable safety devices.

PLACE OF INSTALLATION

T

 

TBSS

 storage cylinders can be installed in any 

room where there is no specific requirement for an electrical 

protection rating higher than IP X0D.

≥ 0,3 m

≥ 0,3 m

≥ 0,3 m

≥ 0,6 m

≥ 0,7 m

NOTE:

 the above-indicated dimensions are recommended for 

a correct maintenance and access to the device.

INSTALLATION IN OLDER SYSTEMS AND 

SYSTEMS REQUIRING MODERNISATION

When installing 

T

 

TBSS

 storage cylinders in old 

systems or systems requiring modernisation, always perform 

the following checks.

- Make sure that the system is fitted with safety and con-

trol devices in accordance with applicable legislation 

and standards

- Make sure that the central heating circuit has been 

flushed out to remove all sludge and lime scale, and 

has been vented and seal tested

- Make sure that a suitable water treatment system is in-

stalled if the quality of the supply/recirculation water so 

demands. (Refer to the reference values listed in the 

table alongside.)

WATER QUALITY REQUIREMENTS

REFERENCE VALUES

pH

6-8

Electrical conductivity

less than 200 μS/cm (25°C)

Chlorine ions

less than 50 ppm

Sulphuric acid ions

less than 50 ppm

Total iron

less than 0.3 ppm

Alkalinity M

less than 50 ppm

Total hardness

less than 35°F

Sulphur ions

none

Ammonia ions

none

Silicon ions

less than 30 ppm

The values above ensure proper operation of the system. Refer 

to the limit values specified in the current standards and regu-

lations on the installation site.

Installation

Summary of Contents for TBSS 150

Page 1: ...TBSS 150 200 300 430 550 TBSS 800 1000 TBSS INSTALLATION OPERATION AND MAINTENANCE MANUAL...

Page 2: ...to property or injury to persons or ani mals caused by improper installation adjustment main tenance or use b The product must be serviced at least once a year Servic ing must be arranged in advance...

Page 3: ...rosion magnesium anode IDENTIFICATION The T TBSS solar heaters can be identified by Data plate This lists the technical specifications and performance of the product BALLON Modele Model Fabrication Co...

Page 4: ...Continuous availability of domestic water DHW 10 45 C at the different coil inlet temperatures and with the indicated delta T Coil delivery temperature 80 C T 20 C 27 39 49 56 66 69 75 kW 660 950 118...

Page 5: ...ed to 55 C coil probe point reference and primary exchanger at the indicated delivery temperature considering an increase of the domestic water temperature of 30 C between inlet and outlet according t...

Page 6: ...ooth open Apply the upper insulation 2 and the upper cover 5 in order to insert the cover exert a light and homoge neous pressure Close the interlocking flaps L completely which were previously left w...

Page 7: ...431 561 635 622 717 641 706 mm E 523 687 793 780 875 799 864 mm F 663 827 993 980 1075 969 1034 mm G 920 1170 1670 1440 1784 1707 2032 mm H 1088 1338 1838 1644 1988 1835 2155 mm I 604 604 604 755 755...

Page 8: ...t are all open Switch the electricity supply ON at the mains power switch and at control panel switch if fitted TEMPORARY SHUTDOWN To reduce to the environmental impact and save energy in case of brie...

Reviews: