15 

|

 

P a g e

                                                                                   

Function 

Operation 

Parameter

 

Menu 

Location 

Factory 
Default 

Operating 

Range 

Unit 

Auxiliary 

Differential 

Heater or Dry Contact 

Hysteresis 

*1

 

Shy 

Hidden 

Menu 2 

1 - 45 

°F 

Maximum 

Temperature 

Alarm 

Alerts with “HA” when 

maximum temperature has 

been exceeded 

ALU 

Hidden 

Menu 2 

105 

45 - 302 

°F 

Minimum 

Temperature 

Alarm 

Alerts with “LA” when 

minimum temperature has 

been exceeded 

ALL 

Hidden 

Menu 2 

45 

-67 - 105 

°F 

 

*1

Note:

 When both Heater and Dry Contact options are included, these parameters only control Heater 

Settings.  Dry Contact is controlled by ALU.

 

 
 

      Alarms Signals 

Message 

Cause 

Outputs

 

“P1” 

Enclosure Probe Failure 

Start and stop of the compressor after 15 minute 

intervals 

*2

 

“P2” 

Condenser Probe Failure 

No Output

 *2

 

“HA” 

Maximum Temperature Alarm: P1 > 105°F for 3 

minutes (after initial 30 min. start up delay) 

No Output

 *2

 

“LA” 

Minimum Temperature Alarm: P1 < 45°F for 3 

minutes (after initial 30 min. start up delay) 

No Output

 *2

 

“HA2” 

Condenser High Temperature Alarm: P2 > 145 °F for 

3 minutes 

Compressor Off

 *2

 

“LA2” 

Condenser Low Temperature Alarm: P2 < 50°F for 3 

minutes 

No Output

 *2

 

“CA” 

Evaporator Coil Alarm: Low Pressure for 3 minutes 

Compressor Off

 *2

 

“noP” 

Invalid Probe Selected: Low Evaporator Coil  

No Output, Display Only 

 

*2

Note:

 When both Heater and Dry Contact options are included, Dry C ontact (Alarm Contact) Relay is 

activated.

 

 

 

ALARM RECOVERY

…….. 

 

If the compressor is turned off due to an alarm, it will be able to restart after the 

AC

 anti short-cycle time delay. 

(Parameter AC = 5minutes) 

 

 

Probe 

alarm

 P1

 is cleared with no time delay after the fault is cleared. 

 

Probe 

alarm 

P2

 starts and stops with no time delay. 

 

Temperature 

alarm 

HA 

automatically clears as soon as the temperature returns to below 105

°F (the 

ALU

 setpoint) -2°F = 103°F. 

 

Temperature 

alarm 

LA 

automatically clears as soon as the temperature returns to above 55

°F (the 

ALL

 setpoint) +2°F = 47°F. 

 

Temperature 

alarm 

HA2 

automatically clears as soon as the condenser coils temperature returns to below 135

°F. 

 

Temperature 

alarm 

LA2 

automatically clears as soon as the condenser coils temperature returns to above 60

°F. 

 

Temperature 

alarm 

CA 

automatically clears as soon as the pressure returns to normal.

 

 
 
 

Summary of Contents for CS011126

Page 1: ...User Technical Manual CS011 Series Rev 1 2...

Page 2: ...tement of Confidentiality The Manual and other materials contain proprietary information comprising Thermal Edge Inc s trade secrets Please maintain the confidentiality of all proprietary information...

Page 3: ...the Air Conditioner 4 Moving the Air Conditioner 5 Unit Label 5 Operation 6 Preliminary Testing 6 Mounting the Air Conditioner 7 Unit Specifications 8 Options 10 System Faults 13 Digital Temperature C...

Page 4: ...ecting the Equipment Thermal Edge air conditioning equipment is designed manufactured and packed to prevent damage from normal handling shock and vibration during shipment It is necessary to inspect y...

Page 5: ...degree angle rotary compressors without damaging the compressor If air conditioner is to be shipped or transported at any time pack in original packaging and strap to pallet to prevent damage Air con...

Page 6: ...ith a Condensate Removal System that changes the excess humidity liquid into a vapor which is then vented to the atmosphere In the event of excess water vapor when the enclosure door has been left ope...

Page 7: ...e air conditioner high on the enclosure in order to cool the hot air at the top of the enclosure Position the unit where the cold air can circulate across the width of the enclosure to cool it all the...

Page 8: ...131 F Unit Weight 30 lbs 120VAC Model Operating Voltage Range Volts Inrush Current Start Up Current Amps Loading Current Running Current Amps SCCR Short Circuit Current Rating Amps Recommended Fuse S...

Page 9: ...d Drive Irving Texas 75038 972 580 0200 888 580 0202 Fax 972 580 0277 URL www thermal edge com Email thermaledgeinfo thermal edge com SP ENG 211 000 02 Rev 1 2 9 P a g e THIS PAGE IS INTENTIONALLY LEF...

Page 10: ...e low ambient package is designed to provide an optimum constant low current in the compressor motor during the non cooling state This option provides internal heat to the compressor to protect it fro...

Page 11: ...ters are ideal for focusing on individual sections of the enclosure without having a large capacity Built in Heater External Heater capacities available are 100 Watt 150 Watt 200 Watt 250 Watt 300 Wat...

Page 12: ...vides the ability to communicate with the Thermal Edge Air Conditioner controller via the Ethernet IP protocol You can monitor and control all settings from a remote location with a PLC Full specifica...

Page 13: ...nute time delay A thermal overload protects the compressor against faults In the event that the snowflake status LED is not flashing on the display and the compressor is not running an internal fault...

Page 14: ...ET key to display its value 4 Use the UP or DOWN arrow key to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds...

Page 15: ...l 30 min start up delay No Output 2 HA2 Condenser High Temperature Alarm P2 145 F for 3 minutes Compressor Off 2 LA2 Condenser Low Temperature Alarm P2 50 F for 3 minutes No Output 2 CA Evaporator Coi...

Page 16: ...s use high efficiency long life sealed ball bearing fans engineered for optimum performance that require no maintenance Keep fan blades clean for optimal performance Fans are removable and attached by...

Page 17: ...025 1 Compressor 31003 1 for 120VAC Compressor Thermal Overload 31003 2 for 120VAC Gasket Installation Kit 71410 CS01 Evaporator Fan 41002 1 1 for 120VAC Condenser Fan 41002 1 1 for 120VAC Note Qty 2...

Page 18: ...is on position ON OFF Toggle Switch then Retry Verify input power meets voltage requirements as shown in the UL label YES If problem is still present contact technical support Unit Overheats Insuffic...

Page 19: ...pressor Use meter 3 Check for faulty evaporator fan 3 Measure Temperature at Evaporator Verify Heat Load Requirements Is unit capacity adequate for internal head load Possible low refrigerant Is compr...

Page 20: ...behind controller CA YES NO Check Low Pressure Switch Connections and Verify Pressure switch is closed Use meter 3 P1 or P2 NO YES Check probe connections potential faulty probe LA LA2 HA HA2 YES Ref...

Page 21: ...Physical Dimensions 120 VAC Models Water overflow excessive Check drain is it plugged YES NO Clean condensate pan and drain add 1 tbsp bleach to upper pan monthly to kill mold Is Air Conditioner seal...

Page 22: ...d Drive Irving Texas 75038 972 580 0200 888 580 0202 Fax 972 580 0277 URL www thermal edge com Email thermaledgeinfo thermal edge com SP ENG 211 000 02 Rev 1 2 22 P a g e THIS PAGE IS INTENTIONALLY LE...

Page 23: ...hermal edge com SP ENG 211 000 02 Rev 1 2 23 P a g e Electrical Schematics System Schematic Digital Controller Schematic Note Schematics apply to all voltages optional accessories wiring not provided...

Page 24: ...the repair or replacement of its own product This Warranty does not cover Labor or reimbursement of labor for evaluation removal installation repair or cost of any warranted part except at the Therma...

Page 25: ...r and address Shipping method Pack unit in a suitable packing for shipment preferably the original packaging if available If suitable packing is not available arrange for packaging to be shipped to yo...

Reviews: