21
. Venting
(continued)
Table 6: Vent and Combustion Air Pipe Diameters and Maximum Lengths
Table 7: Equivalent lengths of Vent and Combustion Air Components
Component
Combustion Air
Vent
Equivalent
Length Per
Piece
x Quantity =
Subtotal
Equivalent
Length
Equivalent
Length
Per Piece
x Quantity
=
Subtotal
Equivalent
Length
Straight Pipe
x
=
A
x
=
D
90° Elbow
x
=
B
x
=
E
45° Elbow
x
=
C
x
=
F
Combustion Air Total
Equivalent Length =
Vent Total
Equivalent Length
=
Notes:
1. Total equivalent length cannot exceed maximum equivalent length shown in Table 6.
2. Combustion air and vent terminations do not count towards total equivalent length.
AMP
Model
Combustion Air Length
Vent Length
Pipe Dia.
in. (mm)
Minimum
ft. (m)
Maximum
ft. (m)
Pipe Dia.
in. (mm)
Minimum
ft. (m)
Maximum
ft. (m)
1000
8 (200)
0
150 (45.7)
8 (200)
3 (0.9)
150 (45.7)
6 (160)
0
70 (21.3)
6 (160)
3 (0.9)
70 (21.3)
1250
8 (200)
0
150 (45.7)
8 (200)
3 (0.9)
150 (45.7)
6 (160)
0
50 (15.2)
6 (160)
3 (0.9)
50 (15.2)
1500
8 (200)
0
150 (45.7)
8 (200)
3 (0.9)
150 (45.7)
6 (160)
0
50 (15.2)
6 (160)
3 (0.9)
50 (15.2)
2000
8 (200)
0
100 (30.5)
8 (200)
3 (0.9)
100 (30.5)
2500
10 (250)
0
150 (45.7)
10 (250)
3 (0.9)
150 (45.7)
3000
10 (250)
0
150 (45.7)
10 (250)
3 (0.9)
150 (45.7)
3500
12 (315)
0
150 (45.7)
12 (315)
3 (0.9)
150 (45.7)
4000
12 (315)
0
150 (45.7)
12 (315)
3 (0.9)
150 (45.7)
NOTE:
Contact factory for assistance on maximum vent length applications.
This table applies to all listed vent/combustion air system options.
Table 8: Vent and Combustion Air Equivalent Length Calculation Worksheet
Diameter
6 in. (160 mm)
8 in. (200 mm)
10 in. (250 mm)
12 in. (315 mm)
90
°
Elbow
7 ft. (2.1 m)
11 ft. (3.4 m)
14 ft. (4.3 m)
18 ft. (5.5 m)
45° Elbow
3 ft. (0.9 m)
4 ft. (1.2 m)
5 ft. (1.5 m)
7 ft. (2.1 m)
Summary of Contents for AMP 1000
Page 85: ...85 Notes...