Thermal Gas Systems HALOGUARD Series Instruction Manual Download Page 3

                   

                                                  3                                                    

Rev.2 1/26/98

 

UNPACKING INSTRUCTIONS

 

 

Haloguard

TM

 monitors are carefully packed, inspected and delivered to the carrier in good condition.  

If damage occurs in transit it is the responsibility of the carrier. 

 

Carefully inspect the unit upon receipt.  Any damage should be reported to the carrier and an 

inspection requested.  After inspection by the carrier and your receipt of his acknowledgment as to 

the damage, contact us for return authorization (RMA).  We cannot file claims for damaged goods 

on your behalf, but we will assist you in any way we can. 

 

In order to expedite our work, please provide serial number and purchase date when you call.   

 

WE CANNOT ACCEPT RETURNS WITHOUT PRIOR APPROVAL

 

BEFORE INSTALLATION 

 

1.  Remove Haloguard

 Controller and IR Sensor Module from carton.  Check contents against 

packing list.  If shipment is incomplete, contact us immediately. 

2.  The following tools and hardware are required for installation and calibration. 

a.  Two standard & one philips screwdrivers; 1 - medium standard w/ long shaft, 1 - jewelers 

fine standard & 1 - medium philips. 

b.  Needle-nosed electrician’s pliers 

c. (8) No. 8

 

x 1” Screw (minimum) 

d.  Digital VOM 

3.  Select a site for the installation: 

a.  Power requirements: Provide a clean source of 115-230 VAC, 50/60 Hz, single phase circuit 

rated 15A minimum  Haloguard

 Controller and IR Sensor Module. 

b.  Infrared (IR) Sensor Module should be mounted near potential leaks in a quiet area or 

downstream from leak source in area with air movement. 

c.  Infrared (IR) Sensor Module sample tube end should be located 18” - 24” above the floor .  If 

using optional scanner, locate IR Module at a point central to chiller locations.  Install inlet 

extension tube out to each remote sample location (up to 200 Ft. from IR module). Make sure 

each sample tube is equipped with an end of line filter. 

d.  Make sure the area selected is not subject to flooding, potential impact or severe ambient 

temperature and humidity changes (i.e. boiler blow-down or near roll-up doors).

 

e.  Infrared detector is highly selective but may respond to the presence of other gases (i.e. paint 

thinner, cleaning fluids and other refrigerants) if interfering gas reaches a high concentration.  

For accurate refrigerant leak detection select a location free from above fumes or temporarily 

disable sensor when they are present.  Contact TGS for specific interference’s. 

4.  The wall mounted controller should be installed indoors, approximately five feet above the floor 

or at a location easily visible to operators, in an area with minimal vibration, and with 

temperature and humidity changes like sensor location. 

 

 

IMPORTANT 

CONSULT LOCAL AND NATIONAL ELECTRICAL CODES FOR ANY SPECIAL 

REQUIREMENTS OR RESTRICTIONS BEFORE INSTALLING HALOGUARD

 

 

 

Summary of Contents for HALOGUARD Series

Page 1: ...G as Type 1 R 11 2 R 12 3 R 22 4 R 134a 5 6 7 R 123 Range 1 0 1000 ppm M ount 1 W all O utputs 11 4 x 3A Relays 12 0 5 VDC or 0 10 VDC 13 4 20mA O ptions Accessories A Audible Alarm B UPS E Inlet Outl...

Page 2: ...n 10 5 Testing 10 6 Trouble Shooting 10 7 Specifications 11 FIGURES Page 1 Dimension Drawing 4 2 Controller Upper Circuit Board 5 3 Controller Lower Circuit Board 5 4 Controller LCD Display Features 6...

Page 3: ...ase circuit rated 15A minimum Haloguard Controller and IR Sensor Module b Infrared IR Sensor Module should be mounted near potential leaks in a quiet area or downstream from leak source in area with a...

Page 4: ...d relay when installed TLV TWA Alarm is factory set and not user adjustable e OFFSCALE LED and Relay Factory set at 1000ppm f RESET Push button Silences alarm disables relays and resets instrument for...

Page 5: ...Lower Circuit Board RUN GAS ALARM ZERO SPAN AUD J5 ANALOG VOLT mA I C Offscale LED Alarm 2 LED Alarm 1 LED Power LED Fault LED Test Button IR Trim Analog Trim Pot 0 5 or 0 10 VDC UP ENTER DOWN Sensor...

Page 6: ...ailure Scan Stop Gas Type R 11 R 12 R 123 R 134 etc Figure 4 Controller LCD Display Features 8 hr TWA Concentration R 123 Concentration ppm Channels 1 8 Optional Scanner Only Flashing cursor means Aut...

Page 7: ...face plate from Haloguard Controller and IR Sensor Module using screw driver 2 Run cable from Haloguard Controller to IR Sensor Module location Eight feet 8FT of cable with DIN connectors standard op...

Page 8: ...tting Figure 8 Press TEST button until LATCH ON appears on the LCD Display LATCH ON mode requires manual RESET of all alarms 2 Analog Output optional is factory set at 0 5 VDC or 4 20mA as ordered Use...

Page 9: ...troller Terminal Provided Wire Color Extension Wire Color Function SCAN Red Red Scanner SIG White White Signal GND Blk Blk Black Ground Note SCAN Terminal is used with scanner Only Figure 6 Sensor Cab...

Page 10: ...allowing sufficient warm up time c Poor sensor location To check Zero Calibration fill a clean plastic trash bag with clean outside air tie off with twist tie let sample stabilize inside for 15 20 min...

Page 11: ...on condensing Controller 0o F to 120o F Non condensing Fault Diagnostics Indicator Light or LCD Readout for fault diagnostics See Figure 5 Materials IR Module NEMA 4 12 13 IP 65 Design Controller NEMA...

Page 12: ...OFFSCALE ALARM 2 Notes 1 Power Cord Provided w wall plug connector and 8 Ft 3 conductor wire 2 Audible and Visual Alarm Optional factory wired Remote Audible and Visual Alarms must be 120VAC and conne...