Thermal Gas Systems HALOGUARD IR Instruction Manual Download Page 1

Rev.1/26/01

1

HALOGUARD

TM

 IR

MULTI-POINT, COMPOUND SPECIFIC MONITOR

INSTRUCTION MANUAL

S E R IA L   N O .

M O D E L   N O .

T em p .  R a n g e

1   -  =   >   6 0

o

F

2   -  =   4 0   -  6 0

o

F

3   -  =   <   4 0

o

F

 

G a s  T yp e

1     -  R -1 1
2     -  R -1 2

R a n g e

3     -  R -2 2               1 -0 -1 0 0 0 p p m
4   -    R -1 3 4 a
5     -  R -1 1 3
6     -  N H 3
7     -  R -1 2 3

                          

O u tp u ts

1   -  4   x   5 A   R elays
2   -  0   –   5 /1 0   V D C
3   -  4   -  2 0 m A
4   -    R S 2 3 2 /4 8 5
5   –   7   x   1 0 A.

O p tion s/A c ce ssor ies

    A   -  Au d ib le  Alarm
    B   –   B atte ry  B /U -U P S
  E  - In le t/O u tle t E x te n sion
  L - S trob e Ligh t
    S   -  S ca n n er
    R   –   R em ote  E x p an sion
         M od u le

11285 Elkins Road  Bldg. H-1

Roswell, GA 30076

TEL:  770-667-3865

FAX: 770-667-3857

www.thermalgas.com

Summary of Contents for HALOGUARD IR

Page 1: ...2 R 12 Range 3 R 22 1 0 1000ppm 4 R 134a 5 R 113 6 NH3 7 R 123 O utputs 1 4 x 5A Relays 2 0 5 10 VDC 3 4 20mA 4 RS232 485 5 7 x 10A O ptions Accessories A Audible Alarm B Battery B U UPS E Inlet Outl...

Page 2: ...6 Calibration Testing Trouble Shooting 10 7 Maintenance Specifications 11 FIGURES Page 1 Typical Area Monitoring Installation 3 2 Mounting Dimensions 4 3 LCD Display Information 4 4 Haloguard IR 5 5 A...

Page 3: ...ed near potential leaks in a quiet area or downstream from leak source in area with air movement c Sample tube pick up should be located 18 24 above the floor If using optional scanner locate sample t...

Page 4: ...tdown Alarms are automatically reactivated if alarm condition is not corrected Reset is automatically initiated on start up and after power failure 7 Optional Display Features TWA Integration Haloguar...

Page 5: ...gital Output 4 20mA 0 5VDC RS 232 485 serial Opt Relay Binary Output 4x5A dry contact Std 7x10A dry contact Opt Power In 120 230Vac 50 60Hz Reset Silence Pushbutton Test Pushbutton Sample Outlet Enclo...

Page 6: ...ng Route wire through entry indicated Figure 4 Remove safety cover All connections are made to the terminal block labeled IN 120 250VAC Figure 6 Connect HOT AC wire to Terminal L Connect NEUTRAL wire...

Page 7: ...with power cord provided c On power up RESET and 20 minute count down will appear on LCD For 20 minutes after power up all alarms and relays are automatically disabled Whenever power is disrupted RES...

Page 8: ...cted turns alarm off 5 CAL Install optional activated charcoal filter in channel 1 follow on screen directions to zero calibrate using ENTER pushbutton 6 SPAN Key and instructions for use are included...

Page 9: ...void nuisance alarms remove alarm jumper AUD before beginning To compensate for line losses adjust signal voltage with a digital VOM as follows 1 Open cover on Remote IR expansion module Move jumper f...

Page 10: ...tall in accordance with instructions b Not allowing sufficient warm up time c Poor sensor location To check Zero Calibration fill a clean plastic trash bag with clean outside air tie off with twist ti...

Page 11: ...11 Accessories SPECIFICATIONS Technology Narrow band Photoacoustic Infrared Electrical Supply 115 230 VAC 50 60Hz Output Signal Std 4x3A Dry Contact SPDT Opt 7x10A Dry Contact SPDT Analog Output Opt...