1751 Hurd Drive ● Irving, Texas 75038 ● (972) 580-0200 ● (888) 580-0202 ● Fax (972) 580-0277
URL: www.thermal-edge.com ● Email:
SP-ENG-211-000-10 Rev 1.1
8
|
P a g e
CAUTION
If mounting the air conditioner to the enclosure door, confirm with the enclosure manufacturer that the
door’s hinges will support the air conditioner’s added weight (see equipment specifications). Insure
that when the door is fully open that the enclosure will not topple over due to the off-center load.
Unit Specifications
The following table provides electrical and refrigeration specifications for the WF081 Series Air
Conditioners.
WF081Series
Nominal Capacity Rating: 8,000 BTUH
Standard Maximum Ambient: 131°F
Model
Operating
Voltage
Range
(Volts)
Inrush
Current
(Start
Up
Current)
(Amps)
Loading
Current
(Running
Current)
(Amps)
SCCR
(Short
Circuit
Current
Rating)
(Amps)
Recommended
Circuit
Protection
(Amps)
KVA
Rating
(K-
Watts)
Refrigerant
Type
Refrigerant
Amount
(ounces)
Low/High
Unit
Pressures
(psi)
Noise
Level
(dBA)
Weight
(Unit/Ship
(lbs)
WF081126
108-132
36.60
12.3
*2
20 Amp Class
CC, CCMR Time
Delay *
1.5
MO99
30.5
144/275
79.5
120/136
WF081236
207-253
19.83
6.0
*2
10 Amp Class
CC, CCMR Time
Delay *
1.5
MO99
32.0
144/286
79.5
145/161
* Time-delay Fuses with the following electrical characteristics are recommended. Fast -acting fuses
are not recommended.
% of Ampere Rating
Opening Time
110 %
15min Minimum
125 %
1hr Maximum
200 %
12sec Minimum
4min Maximum
*2
SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel /
enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.