CAUTION
If mounting the air conditioner to the enclosure door, confirm with the enclosure manufacturer that the
door’s hinges will support the air conditioner’s added weight (see equipment specifications). Ensure
that when the door is fully open that the enclosure will not topple over due to the off-center load.
Unit Specifications
The following table provides electrical and refrigeration specifications for the NE050, NE060 & NE080
Series Air Conditioners.
NE050Series
Nominal Capacity Rating: 5,000 BTUH
Standard Maximum Ambient: 125°F
Unit Weight: 120VAC
– 97lbs, 230VAC – 92lbs, 480VAC – 136lbs
Model
Operating
Voltage
Range
(Volts)
Inrush
Current
(Start
Up
Current)
(Amps)
Loading
Current
(Running
Current)
(Amps)
SCCR
(Short
Circuit
Current
Rating)
(Amps)
Recommended
Fuse Selection
(Amps)
KVA Rating
Refrigerant
Type
Refrigerant
Amount
(ounces)
Low/High
Unit
Pressures
(psi)
NE050126
110-120
23.42
7.26
*2
12 Amp Class
CC, CCMR
Time Delay *
0.85
R422d
12.50
188 / 300
NE050236
220-240
19.15
3.76
*2
10 Amp Class
CC, CCMR
Time Delay *
0.7
R422d
12.50
188 / 390
NE050486
440-480
9.18
1.44
*2
5 Amp Class
CC, CCMR
Time Delay *
0.7
R422d
12.50
188 / 390
* HACR Type Circuit Breakers or Time-delay Fuses with the following electrical characteristics are
recommended. Fast-acting fuses are not recommended.
% of Ampere Rating
Opening Time
110 %
15min Minimum
125 %
1hr Maximum
200 %
12sec Minimum
4min Maximum
*2
SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel /
enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.