background image

7.4 Refrigerant Charging 

If the refrigerant charge is lost due to service or a leak, a new charge 
must be accurately weighed in. If any of the old charge is left in the 
system, it must be recovered before weighing in the new charge. 
Refer to the unit nameplate for the correct charge weight and 
refrigerant type. 

7.5 Impeller Fan Replacement 

The motorized impeller fan is a unitary assembly consisting of the 
motor and impeller fan. If defective, the complete assembly must be 
replaced. 

1. Unplug the power cord. 
2. Remove the cabinet access panel. 
3.  Remove the screw attaching the impeller fan support bracket 

to the base. 

4.  Disconnect the impeller fan leads inside the electric box. 
5.  Push up on the inlet ring and pull the impeller fan and impeller 

fan support bracket to the right. 

6.  Align the bracket with the two notches in the front flange of the 

base (behind the foam). 

7. Slide the impeller fan assembly from the unit. 
8.  Remove the defective impeller fan from the bracket and 

replace with it with the new impeller fan. 

9.  Reassemble the new impeller fan by reversing the above 

procedure. Note: There are two pins on the backside of the 
cabinet that must align with the two holes in the impeller fan 
support bracket. 

7.6 Compressor/Capacitor Replacement 

This compressor is equipped with a two terminal external overload 
and a run capacitor, but no start capacitor or relay (See Figure 4). 

7.6A Checking Compressor Motor Circuits 

Perform the following tests if the impeller fan runs but the 
compressor does not with the fan switch and ventilation timer OFF 
and the humidity control ON. 

1.  Unplug the unit; remove the cabinet side and the electrical 

connection cover on the compressor top. 

2.  Plug in the unit and turn the humidity control to ON. Check for 

110 volts from compressor terminal R to overload terminal 3 
using an AC voltmeter. If voltage is present, go to step 3. If no 
voltage, there may be a loose connection in the compressor 
circuit. Test each component for continuity. See the appropriate 
section if a defect is suspected. 

3.  Unplug the unit, and then disconnect the red and yellow wires 

from compressor terminals R & S. Using an ohmmeter check 
continuity between the points listed below. 

4.  Compressor terminals C and S: No continuity indicates an open 

start winding. The compressor must be replaced. Normal start 
winding resistance is 3 to 7 ohms. 

5.  Compressor terminals C and R: No continuity indicates an open 

run winding. The compressor must be replaced. Normal run 
winding resistance is .5 to 2 ohms. 

6.  Compressor terminal C and overload terminal 1: No continuity 

indicates a defective overload lead. 

7.  Overload terminals 1 and 3: If there is no continuity, the 

overload may be tripped. Wait 10 minutes and try again. If 
there is still no continuity, it is defective and must be replaced. 

8.  Compressor terminal C and compressor case: Continuity 

indicates a grounded motor. The compressor must be replaced. 

9.  Disconnect the wires from the run capacitor. Set the ohmmeter 

to the Rx1 scale. The capacitor is shorted and must be 
replaced if continuity exists across its terminals. If there is no 
needle movement with the meter set on the Rx100000 scale, 
the capacitor is open and must be replaced. 

10.  Reconnect the wires to the compressor and capacitor. Plug in 

and turn on the unit. If the compressor fails to start, replace 
the run capacitor. 

11.  If the unit still does not start, adding a hard-start kit (relay & 

capacitor) will provide greater starting torque. If this doesn't 
work, the compressor has an internal mechanical defect and 
must be replaced. 

7.6B Replacing a Burned Out Compressor 

The refrigerant and oil mixture in a compressor is chemically 
very stable under normal operating conditions. However, when an 
electrical short occurs in the compressor motor, the resulting high 
temperature arc causes a portion of the refrigerant oil mixture to 
break down into carbonaceous sludge, a very corrosive acid, and 
water. These contaminants must be carefully removed otherwise 
even small residues will attack replacement compressor motors and 
cause failures. 

The following procedure is effective only if the system is monitored 
after replacing the compressor to insure that the clean up was 
complete. 

1.  This procedure assumes that the previously listed compressor 

motor circuit tests revealed a shorted or open winding. 

2.  Remove and properly dispose of the system charge. DO NOT 

vent the refrigerant or allow it to contact your eyes or skin. 

3.  Remove the burned out compressor. Use rubber gloves if there 

is any possibility of contacting the oil or sludge. 

4.  To facilitate subsequent steps, determine the type of burn 

out that occurred. If the discharge line shows no evidence 
of sludge and the suction line is also clean or perhaps has 
some light carbon deposits, the burn out occurred while the 
compressor was not rotating. Contaminants are therefore 
largely confined to the compressor housing. A single 
installation of liquid and suction line filter/driers will probably 
clean up the system. 

FOR HVAC INSTALLER ONLY

17

Ultra-Aire 150H Installer’s & Owner’s Manual

Summary of Contents for Ultra-Aire UA-150H

Page 1: ...e unit The Ultra Aire 150H is controlled by 24 volt remote wired controls A variety of controls are available suitable to various applications Fresh Air Ventilation Optional fresh outdoor air may be ducted to the unit via a six inch round duct This provides fresh air to dilute pollutants and maintain high oxygen content in the air The amount of fresh air ventilation can be regulated by a variety o...

Page 2: ...ing and Operation 13 5 3G Fan On Fan Off Fan Program 13 5 3H Damper Operation and Setting 13 5 3I Intermittent Programmed Ventilation 14 5 3J Programming Notes 14 5 3K Ventilating or Dehumidifying to Control Indoor Relative Humidity Levels 14 5 3L Stop Start 14 5 3M Low Pressure Control 14 6 Maintenance 15 6 1 Standard Air Filter 15 6 2 High Efficiency Air Filter 15 6 3 Impeller Fan Oiling 15 6 4 ...

Page 3: ... the front panel for maintenance and service DO NOT INSTALL UNIT WITH THE FRONT PANEL INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain there is NO chance the unit could fall into the water splashed and that it is plugged into a GFI GROUND FAULT INTERRUPT OUTLET DO NOT use the device as a bench or table DO NOT place the d...

Page 4: ...tape or a suitable alternative from structural members Remember to place a drain pan under the unit if it is suspended above a finished area or above an area where water leakage could cause damage The UA 150H should be located near the existing air handling system to minimize the required ductwork for connecting the UA 150H to the existing air handling system The controls for the UA 150H are remot...

Page 5: ...UA 150H and fold the tabs up to attach to UA 150H 3 4B Ducting for Dehumidification For the ideal installation draw air from the central part of the home and return it to the isolated areas of the home like the bedrooms den utility room or family room The ductwork of the existing heating system can be used to supply air to the home If the existing supply goes to isolated areas of the home discharg...

Page 6: ...e inside and outside air conditions Consult the factory by calling 1 800 533 7533 for recommendations regarding the use of higher flows with your specific application The outside air duct should be connected to the 6 round collar on the filter enclosure of the unit The 6 round collar includes a manual damper Adjust the manual damper to provide the desired amount of fresh air for ventilation The am...

Page 7: ... ties to secure it during shipment This rigid attachment is not necessary once the unit is installed and may cause noise from compressor vibration After installation cut the cable ties to free the compressor from the cabinet REMOVE THE HORIZONTAL CABINET SUPPORT TO WHICH THE COMPRESSOR IS ATTACHED The ends of the support are notched so that the support can easily be removed Cut the strips of metal...

Page 8: ...nded Quality humidity meters are available from the factory and are recommended to accurately monitor humidity levels 4 4 Fan Filter Switch Turning ON the fan filter switch will cause the the UA 150H impeller fan to run continuously whether the UA 150H is dehumidifying or not This function is desirable if the unit is used for air circulation and filtration to achieve maximum indoor air quality Whe...

Page 9: ... the number 1 should remain in the lower right hand corner of the display The 1 and OFF signify the turn off time for the first program Set the turn off time using the 1 7 h and m buttons in the same way as described above and continue on to the second through sixth programs When setting the ventilation programs you can return to the current time display by sliding the switch in the upper right co...

Page 10: ...LOW ATTENTION INSTALLER WARNING DO NOT allow the yellow lead from the unit to contact the red lead or the white lead from the unit or damage to the transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation control or damage to the transformer will result ...

Page 11: ...1 8 from the wall or flat surface 6 Align the back panel against these screws pushing it forward allowing it to slide downward to lock into position 7 Make the electrical connections to the terminals on theback panel as shown in the wiring diagram 8 Seal the hole around the wires to prevent air movement 9 Reconnect the quick connector onto the back panel 10 Reassemble the front to the back panel C...

Page 12: ... temperature The fan status display is indicated by a capitol F OF indicates fan off status on indicates fan on status The damper display is indicated by a d with the same on off status indicators as the temperature The ventilation program is displayed along the bottom of the display during the clock humidity and temperature displays only when the damper operation is set to the programmed setting ...

Page 13: ...indicate the current fan setting it indicates the current fan status and will always read either on or off With the fan in the on mode the fan will run continuously This does not effect the dehumidification functions of the system The system may or may not be ventilating or dehumidifying while the fan is running Common reasons for operating the fan continuously are continuous filtration and air re...

Page 14: ...remember any changes and return to home state 5 3J Programming Notes To run the ventilation program the damper mode must be in the program mode Pr The timer can be operated manually without changing the program by adjusting the damper mode from program to either on or off To delete a program after it has been entered adjust the program so the START and STOP times are identical Occupants should det...

Page 15: ...clean the high efficiency pleated paper filter It should be replaced when it becomes restrictive See Figure 7 6 3 Impeller Fan Oiling The impeller fan motor is factory lubricated for many years of normal operation and no further oiling is required 6 4 Optional Fresh Air Return Check and clean the screen on the outdoor fresh air return seasonally The screen may become plugged during the seasons whe...

Page 16: ...vaporator coil frosted continuously low dehumidifying capacity 1 Defrost thermostat loose or defective Sec 5 8 2 Low refrigerant charge 3 Dirty air filter s or airflow restricted 4 Excessively restrictive ducting connected to unit Unit not providing ventilation Ventilation timer not operating correctly 1 If timer is not functioning correctly reset timer and reprogram Sec 3 5 2 Check control wire c...

Page 17: ... The compressor must be replaced Normal run winding resistance is 5 to 2 ohms 6 Compressor terminal C and overload terminal 1 No continuity indicates a defective overload lead 7 Overload terminals 1 and 3 If there is no continuity the overload may be tripped Wait 10 minutes and try again If there is still no continuity it is defective and must be replaced 8 Compressor terminal C and compressor cas...

Page 18: ...ntrol is out of calibration or the RH is below 40 The UA 150H is equipped with an automatic defrost mechanism If the UA 150H operates in conditions that develop frost on the evaporator it will sense the frost build up and automatically defrost the evaporator The UA 150H may not appear to be operating correctly during the defrost sequence but once the defrost sequence is completed the UA 150H will ...

Page 19: ... Under these conditions the unit will restart within several minutes Until the unit warms up it may cycle several times 7 11 Condensate Pump Kit An optional condensate pump kit is available from the factory for use with the UA 150H Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to close the float switch The pump also contains a safety flo...

Page 20: ...FOR HVAC INSTALLER ONLY 20 Ultra Aire 150H Installer s Owner s Manual Pictorial Electrical Diagrams of UA 150H ...

Page 21: ...21 Ultra Aire 150H Installer s Owner s Manual Wiring Diagrams FOR HVAC INSTALLER ONLY ...

Page 22: ...57 1 Evaporator Coil 10 4024270 1 Impeller Fan 11 4020924 1 Impeller Fan Relay SPDT 24 Vac 15A 12 4024360 1 Impeller Fan Run Capacitor 16MFD 13 4025087 1 Filter Drier 14 4021626 1 Hose Drain Pan 56 ID x 8 15 4024368 1 Inlet Collar 10 Galvanized Steel 16 4023928 1 Inlet Collar 6 Galvanized Steel with Damper 17 4022219 1 Low Pressure Control 18 4021332 1 Outlet Collar 10 Galvanized Steel 19 4022487 ...

Page 23: ...l Panel Assembly Ventilation Timer Humidity 30 4023660 1 Controller Humidity 31 4023672 1 Duct Damper 6 Diameter Electrically Actuated not shown 32 4024153 1 Cover for Items 28 29 not shown 33 4021495 1 Knob Black 25 shaft 34 4024150 1 Instructions Humidity Fan not shown 35 4024122 1 Instructions Ventilation Timer Humidity not shown 36 4025560 1 Switch Black SPDT On Off 37 4022486 1 Timer 7 Day 24...

Page 24: ...f the floor 2 Slide 2 of the nuts over each screw 3 Attach the screws with nuts to the holes located in the bottom corners of the UA 150H 4 Slide the grommet over the screw and nuts assembly 5 Repeat for the other end of the UA 150H VIBRATION ISOLATION KIT UA 150H 24 Ultra Aire 150H Installer s Owner s Manual ...

Page 25: ...A 150H if possible as this is the easiest time to install the insulation kit Install the insulation kit as shown in the illustration below After installing the insulation cut out the holes for the supply and return connections and cut the seam around the removable front cover so it can be removed easily If more insulation is needed two or more insulation kits may be applied to a single UA 150H EXT...

Page 26: ...ATTENTION INSTALLER 26 Ultra Aire 150H Installer s Owner s Manual ...

Page 27: ...lications and does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable control LIMITATIONS AND EXCLUSIONS If any Ultra Aire 150H Dehumidifier part is repaired or replaced the new part shall be warra...

Page 28: ...ermastor com Information in this document is subject to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2006 Therma Stor LLC All rights reserved ...

Reviews: