background image

quest

quest

1-866-933-7486 

Quest PowerDry 4000 Pro 

Installation, Operation and Maintenance Instructions  

5

www.QuestProtect.com

[email protected]

•  It must always be used in the upright position.

•  The air inlet on top and the front outlet must be at least 1 foot from walls and other obstructions to air 

flow.

•  If the humid area is very large, dehumidification can be improved by adding an outlet duct to circulate air 

to stagnant areas (see Sec. 2.5). 

2.3 Electrical Requirements

The Quest PowerDry 4000 

Pro

 can be plugged into a grounded 15 Amp circuit. At 80°F, 60% RH, it draws 

10 Amps. Due to the high percentage of a 15 Amp circuit’s capacity that the unit uses, the circuit should be 
dedicated to running it only. Amp draw decreases at lower loads and increases at higher loads. At extremely 
high loads, a 20 Amp circuit may be required.

If an extension cord is required, it must have a minimum of 12 gauge conductors if 25 feet long or less and 
10 gauge conductors if greater than 25 feet long.

2.4 Condensate Removal

The Quest PowerDry 4000 

Pro

 is equipped with an internal condensate pump to remove the water that is 

condensed during dehumidification. This allows the condensate to be pumped 30’ with the attached hose. 
If the condensate must be pumped more than 20 feet above the unit, a second pump must be added to relay 
the condensate.

2.5 Ducting

A detachable rectangular exhaust collar is supplied that will allow 10” round lay-flat duct to be attached to 
the Quest PowerDry 4000 Pro outlet. 

To attach ducting to a collar, put the plastic duct end through the collar center and roll the duct end outward 
so that it overlaps the outside of the collar. The duct and collar may then be quickly attached to the Quest 
PowerDry 4000 Pro by snapping the collar over the four screws at the blower outlet. 

2.6 Power Button

Press the POWER button to turn the dehumidifier on or off. When starting the dehumidifier the display will 
show the accumulated hours. Press the POWER button again to turn the dehumidifier off. The display will 
also power off.

2.7 Pump Purge Button

During normal operation the pump automatically cycles every four minutes. Press the PURGE button to 
remove condensate manually from the reservoir. There are several ways to manually remove water from the 

reservoir:

1.   Press the PURGE button once and the pump will run for 20 seconds

2.   Press and hold the PURGE button and the pump will run for up to 30 seconds

3.   Press the PURGE button while the dehumidifier is powered off and the pump will run for 30 seconds.

Always manually purge the water reservoir before transport or storage. Turn off the power and allow the 

plugged in dehumidifier to rest 15 minutes before the final purge.

Summary of Contents for Quest PowerDry 4000 Pro

Page 1: ...53704 Toll Free 1 866 933 7486 www QuestProtect com sales QuestProtect com Read and Save These Instructions TS 760 11 14 quest quest 1 Quest PowerDry 4000 Pro High capacity 176 pints day AHAM 22 Gall...

Page 2: ...nsate Removal 5 2 5 Ducting 5 2 6 POWER Button 5 2 7 PURGE Button 5 2 8 Humidistat 6 2 9 HOURS Button 6 2 10 DEFROST Light 6 2 11 Defrost Cycle 6 2 12 Low Pressure Control 6 3 Maintenance 7 3 1 Air Fi...

Page 3: ...s for maintenance and service DO NOT INSTALL UNIT WITH THE SERVICE PANELS INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain...

Page 4: ...d refrigeration system Dimensions Width 20 Depth 23 Height 40 Weight 135 lbs 2 Operation Place dehumidifier inside structure place condensate hose into a drain or a very large container and turn on To...

Page 5: ...mped more than 20 feet above the unit a second pump must be added to relay the condensate 2 5 Ducting A detachable rectangular exhaust collar is supplied that will allow 10 round lay flat duct to be a...

Page 6: ...w the defrost set point due to excessive frost formation the thermistor activates the solid state control and the defrost light The control cycles the compressor off and on by monitoring thermistor te...

Page 7: ...much as possible before storage 1 Use the pump purge switch see Sec 2 7 and Fig 4 to reduce the water level in the reservoir 2 Stretch the hose flat to drain it completely If the unit will not be expo...

Page 8: ...s the entire coil from inlet to outlet The mixture of gas and liquid refrigerant enter the accumulator after leaving the evaporator coil The accumulator prevents any liquid refrigerant from reaching t...

Page 9: ...control board Unit removes some water but not as much as expected 1 Air temperature and or humidity have dropped 2 Check to make sure humidistat is set high enough 3 Humidity meter and or thermometer...

Page 10: ...rnal thermal overload protection If defective the complete assembly must be replaced 1 Unplug power cord 2 Remove the front cover 3 Remove the 5 screws attaching blower inlet ring 4 Remove the 4 screw...

Page 11: ...Gravity Drain Option If the condensate pump fails and cannot be replaced immediately the Quest PowerDry 4000 Pro can be used by draining by gravity 1 Unplug the unit and remove the front cover 2 Push...

Page 12: ...IED OB T STOR ENGRG DEPT 3 PROOFS TO BE APPROVED BY T STOR ENGRG DEPT 4 COLORS BLACK LINES LETTERS ON WHITE BACKGROUND PART NO SHEET REV TITLE DRAWN BY CHECKED BY SIGNATURES DATE SCALE A 1 OF 1 INCHES...

Page 13: ...ompressor 55mfd 370V 1 4029606 13 Capacitor Impeller 15mfd 371V 1 4033031 07 14 Thermistor 1 4032644 15 Cord 1 4032315 16 Compressor 11 9KBTU R410a 1 4029186 17 Overload Compressor 1 4029177 18 Evapor...

Page 14: ...reliable means The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modifica...

Reviews: