23
Technical data
• Operating voltage:
230 –240 V~, +10 %/-15 %
• Frequency:
50–60 Hz
• Power consumption:
ca. 0,4 W
• Standby min.:
ca. 0,4 W
• Switch output:
switching of choice of
external wires is permitted
• Contact:
two way switch
(TR 609 top2 S: NO contact)
• Gap:
<3 mm (µ)
• Contact material:
AgSnO
2
• Max switching capacity: 16 A, 250 V~, cos
ϕ
= 1;
4 A, 250 V~, cos
ϕ
= 0,6
• Min. switching capacity: 10 mA/230 V AC
100 mA/12 V AC/DC
• Incandescent lamp load: 1000 W (TR 609 top2 S: 2000 W)
• Halogen lamp load:
1000 W (TR 609 top2 S: 2000 W)
• Fluorescent lamp load: uncor
series corrected 1000 W
(TR 609 top2 S: 2000 W)
parallel correction 80 W (14µF)
(TR 609 top2 S: 1300 W
(140 µF))
• Compact fluorescent lamps: 30 W
(TR 609 top2 S: 300 W)
• LED lamps (<2W):
6 W (TR 609 top2 S: 55 W)
LED lamps (>2 W < 8 W): 20 W
(TR 609 top2 S: 180 W)
• Permissible ambient temperature:
–25 °C ... +55 °C
• Protection class:
II in accordance with
EN 60730-1 subject to
designated installation
• Protection rating:
IP 20 nach EN 60529
• Time accuracy:
≤
±0,25 s/day at 25 °C
• Power reserve:
10 years (lithium cell)
at +20 °C
• Pollution degree:
2
• Rated impulse withstand voltage: 4 kV
• Max. switching cycles with 16 A
resistive load:
50,000
GB