• To switch the PIR from presence to absence mode, press the
   

lock/unlock

 button and you will see 2 flashes from the LED 

   receiver of the PIR, this indicates that the PIR is unlocked and
   ready to receive further instructions from the remote control.
   Next press the 

Semi Auto

 button on the 

IR10AB

 remote 

   control. The LED  receiver light will flash once for up to 2 
   seconds and dissapear, this indicates that the PIR is now in
   

Semi Auto

 (absence mode).

• When the PIR set to absence mode, the unit will not switch 
   on automatically when someone walks in the detection area. 
• The person in the room must press the retractable push 
   button for the light to switch on. From this point onwards as 
   long as detection in the area has constant movement, the 
   PIR will continue to keep the luminaire or attached load 
   swtiched on, until the subject has moved out of the detection 
   area and the time delay function takes over. 
• For example if set to 10 minutes the PIR will begin to 
   countdown from this value once nothing is in the detection 
   area. If a subject is detected the time delay will reset.

Switching From Presence To Absence Mode:

Switching From Absence To Presence Mode:

• To switch the PIR from absence to presence mode, press the
   

lock/unlock

 button and you will see 2 flashes from the LED 

   receiver of the PIR. Next press the 

Auto

 button on the 

   IR10AB

 remote control. The LED receiver light will flash 

   twice and dissapear, this indicates that the PIR is now in 
   

Auto

 (presence mode). There will be up to a 1 minute delay 

   in changing modes where the PIR will not switch.       

Summary of Contents for TIMEGUARD PDFM361AB

Page 1: ...Presence Detector With Model PDFM361AB 1 Channel Model PDFM362AB 2 Channel I n s t a l l a t i o n O p e r a t i n g I n s t r u c t i o n s Optional Absence Detection 360 Flush Mount PIR...

Page 2: ...eaker turned off It is recommended that a qualified electrician is consulted or used for the installation of this PIR and install in accordance with the current IEE wiring and Building Regulations Che...

Page 3: ...the latest directiives Construction Polycarbonate Dimensions H x W x D 105mm x 105mm x 67mm PIR Ceiling Projection 23 5mm Note Only PDFM362AB supports 2 channel Note Absence mode can only be triggere...

Page 4: ...ensure the best performance from the PIR and the appointed approach path Effective Approach Path ACROSS Ineffective Approach Path TOWARDS Avoid positioning the PIR near any sources of heat in and aro...

Page 5: ...itch should be installed to enable the power to be switched ON and OFF to the PIR This allows the unit to be easily switched OFF for maintenance purposes Mark the position of the 68mm diameter hole cu...

Page 6: ...re sleeved See Section 6 Connection Diagram When wiring is complete close the door entry access points to clamp the cable securely into place Tighten the screws to the door entry points and ensure not...

Page 7: ...61AB Wiring Configuration Load SwitchedLive BrownorRed to Neutral BlueorBlacktoN PDFM361AB PDFM362AB Channel1 230VAC50HzOnly Live BrownorRed toL Neutral BlueorBlacktoN Channel2 VoltFreeInputtoC1 5 230...

Page 8: ...ion area when the PIR is triggered and the load will turn ON for the minimum set amount of time Once you are happy with the pickup area of the PIR you can set the Lux dial in the anticlockwise directi...

Page 9: ...ards as long as detection in the area has constant movement the PIR will continue to keep the luminaire or attached load swtiched on until the subject has moved out of the detection area and the time...

Page 10: ...IR10AB is an optional remote control that is sold separately If absence detection is required the IR10AB will be needed to change modes over LUX control adjustment Auto mode only Time delay adjustmen...

Page 11: ...de of the UK All shipping costs are to be paid in advance before a replacement is sent Problem Cause Solution False activation Luminaire switches on for no apparent reason Heat sources as described in...

Page 12: ...com or call the helpdesk on 020 8450 0515 Qualified Customer Support Coordinators will be online to assist in resolving your query For a product brouchure please contact Timeguard Limited Victory Par...

Reviews: