9
Value range
Automatic detection of push button or switch. A signal that
is present for less than 0.7 s is detected as a push button.
Longer signals are evaluated as a switch.
auto
To adapt to user behaviour, the type
of signal transmitter used can be
set to fixed. Automatic detection is
deactivated.
When selecting the push button,
opening contact or NO contact can also
be specified.
Switch
Push button (NO
contact)
Push button
(opening contact)
Switch
Push button
S
Push button
O
Adjustment possible only with "SendoPro 868-A".
Detection sensitivity
The detector has 5 sensitivity increments. The basic setting is
the middle increment (3).
By selecting the test presence operating mode, the set sensi-
tivity increment is not changed.
Increments 1 to 5 can be selected and sent to the detector
with the «SendoPro 868-A» management remote control.
On the «theSenda P» installation remote control, the sensi-
tivity can be increased or decreased by one increment each
time the button is pushed.
Increment
Sensitivity
1
very insensitive
2
insensitive
3
standard
4
sensitive
5
very sensitive
Room monitoring sensitivity
The detector has 3 sensitivity levels. The basic setting is the
middle increment 2.
Sensitivity increments 1 to 3 can be selected and sent to the
detector with the «SendoPro 868-A» management remote
control.
Increment
Sensitivity
1
insensitive
2
standard
3
sensitive
Description of room monitoring function, see section „Pre-
sence channel“.
Group address channel A
This parameter is applied when using the "theSenda S" user
remote control.
A group address can be assigned to Channel A light.
The "SendoPro 868-A" or "theSenda S" can be used to pro-
gram the group addresses in the detector.
Group address value range
Adjustable values "SendoPro 868-A"
I, II , III , All
Adjustable values "theSenda S"
I, II
LED motion display
The motion detection can be displayed via the LED.
Value range
No display of motion detection.
Off
The LED is switched on when motion is detected, otherwise
switched off.
On
Adjustment possible only with "SendoPro 868-A".
Teach-in channel A
With teach-in, the currently measured brightness value is
accepted as brightness switching value A. Values outside the
permitted range will automatically be set to the appropriate
limit value.
The control command teach-in can be adopted with the
"SendoPro 868-A" management remote control or with the
"theSenda P" installation remote control via the
button.
Factory settings
The presence detector thePrema P360-101 is supplied with
the following parameter values:
Parameter
Value
Brightness switching value A
300 lux
Room correction factor A
0.3
Light measurement
spot
Time delay A
10 min
Short presence A
On
Time delay H
10 min
Switch-on delay H
0 s
Assignment channel A
L‘
Energy saving mode
eco
Configuration type
auto
Staircase light function
Off
Control input S
auto
Detection sensitivity
Increment 3
Monitoring sensitivity reduction
Increment 2
Group address
I
Scene 1
On
Scene 2
Off
LED display motion
Off
9. Start-up
Switch-on behaviour
Every time the sensor unit is inserted into the power supply
unit, or every time the power supply is switched on, the pre-
sence detector runs through two phases that are shown by an
LED: