Theben thePrema P360-101 E UP WH Operating Instructions Manual Download Page 9

9

Value range

Automatic detection of push button or switch. A signal that 

is present for less than 0.7 s is detected as a push button. 

Longer signals are evaluated as a switch.

auto

To adapt to user behaviour, the type 

of signal transmitter used can be 

set to fixed. Automatic detection is 

deactivated.

When selecting the push button, 

opening contact or NO contact can also 

be specified.

Switch

Push button (NO 

contact) 

Push button 

(opening contact)

Switch

Push button 

S

Push button 

O

Adjustment possible only with "SendoPro 868-A".

Detection sensitivity

The detector has 5 sensitivity increments. The basic setting is 

the middle increment (3). 

By selecting the test presence operating mode, the set sensi-

tivity increment is not changed. 

Increments 1 to 5 can be selected and sent to the detector 

with the «SendoPro 868-A» management remote control.

On the «theSenda P» installation remote control, the sensi-

tivity can be increased or decreased by one increment each 

time the button is pushed.

 

Increment

Sensitivity

1

very insensitive

2

insensitive

3

standard

4

sensitive

5

very sensitive

Room monitoring sensitivity

The detector has 3 sensitivity levels. The basic setting is the 

middle increment 2.

Sensitivity increments 1 to 3 can be selected and sent to the 

detector with the «SendoPro 868-A» management remote 

control.

Increment

Sensitivity

1

insensitive

2

standard

3

sensitive

Description of room monitoring function, see section „Pre-
sence   channel“.

Group address channel A

This parameter is applied when using the "theSenda S" user 

remote control.

A group address can be assigned to Channel A light.

The "SendoPro 868-A" or "theSenda S" can be used to pro-

gram the group addresses in the detector.

Group address value range

Adjustable values "SendoPro 868-A"

I, II , III , All

Adjustable values "theSenda S"

I, II

LED motion display

The motion detection can be displayed via the LED.

Value range

No display of motion detection.

Off

The LED is switched on when motion is detected, otherwise 

switched off.

On

Adjustment possible only with "SendoPro 868-A".

Teach-in channel A

With teach-in, the currently measured brightness value is 

accepted as brightness switching value A. Values outside the 

permitted range will automatically be set to the appropriate 

limit value.

The control command teach-in can be adopted with the 

"SendoPro 868-A" management remote control or with the 

"theSenda P" installation remote control via the 

 button.

Factory settings

The presence detector thePrema P360-101 is supplied with 

the following parameter values:

Parameter

Value

Brightness switching value A

300 lux

Room correction factor A

0.3

Light measurement

spot

Time delay A

10 min

Short presence A

On

Time delay H

10 min

Switch-on delay H

0 s

Assignment channel A

L‘

Energy saving mode

eco

Configuration type

auto

Staircase light function

Off

Control input S

auto

Detection sensitivity

Increment 3

Monitoring sensitivity reduction

Increment 2

Group address

I

Scene 1

On

Scene 2

Off

LED display motion

Off

9.  Start-up

Switch-on behaviour

Every time the sensor unit is inserted into the power supply 

unit, or every time the power supply is switched on, the pre-

sence detector runs through two phases that are shown by an 

LED:

Summary of Contents for thePrema P360-101 E UP WH

Page 1: ...option Installation remote control theSenda P option 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electric...

Page 2: ...is switched off automatically Staircase light function The staircase light function can be set to room or corridor using the DIP switch or the SendoPro management remote control Lighting can be switch...

Page 3: ...0 m 100 m2 10 0 m x 10 0 m 1 0 m Brightness measurement The presence detector measures artificial light and daylight that is reflected below the detector The character of the light measurement can be...

Page 4: ...ce detector is insufficient larger rooms then up to 10 detectors can be operated in parallel by connecting P terminals In the process presence detection is performed by all detectors together The mast...

Page 5: ...area covered by one presence detector is insuffi cient larger rooms then up to 10 presence detectors can be operated in parallel as slaves by connecting P terminals Master switches lighting directly...

Page 6: ...function see function description room manual switching on and off possible corridor detector is used as staircase light timer switch Manual switch off is no longer possible DIP switch energy saving b...

Page 7: ...on Can be triggered SendoPro 868 A Can be trigge red the Senda P Presence test Off On x x Light test Off On x Restart Restart detector x x Local settings Detector assumes the set tings of the DIP swit...

Page 8: ...n Adjustable values theSenda P 10 s 30 s 60 s 2 min 10 min 20 min 120 min Switch on delay H The presence channel always switches regardless of whether configuration type is set to fully automatic devi...

Page 9: ...ed when using the theSenda S user remote control A group address can be assigned to Channel A light The SendoPro 868 A or theSenda S can be used to pro gram the group addresses in the detector Group a...

Page 10: ...not be activated in test mode Test mode ends automatically after 10 min The detector performs a new start see switch on behaviour Light test The light test mode is used to check the brightness thresho...

Page 11: ...incandescent lamps halogen spotlights moving objects e g curtains hanging in an open windows Load EBs relays not cleared Push button does not function Device still in the start up phase illuminated pu...

Page 12: ...ww theben de SendoPro 868 A Item No 9070675 Details www theben de theSenda S Item No 9070911 Details www theben de theSenda P Item No 9070910 Details www theben de ThebenHTS AG Im Langhag 7b 8307 Effr...

Reviews: