4
Settings by using theSenda S
theSenda S can only be used to switch the presence detector
on or off (
3
and
2
).
Settings by using theSenda P
Setting the teach-in function
¾
At the desired brightness, press the button (
25
). The
measured brightness value will be accepted as the new
brightness switching value.
Setting the test function
¾
Press the
1
button. The presence detector directly goes
into the test function (see walking test). The test function
ends after 10 min.
Setting fully or semi-automatic device function
Fully automatic: The lighting switches automatically on and
off (neither on the basis of presence/absence nor on the
basis of brightness).
¾
Press button
5
.
Semi automatic: The lighting must always be switched on
manually. Lights are automatically switched off by the pre-
sence detector (due to absence or brightness).
¾
Press button
27
.
New start of detector
¾
Press button
30
.
The detector performs a new start (see switch-on behaviour).
The brightness switching value (LUX) and time delay (TIME)
are reset to the preset values on both potentiometers.
Back to automatic mode
¾
Press button
2
.
The detector ends the walking test or manual override with
the pressing of a button and goes into normal operation
mode.
The following parameters or functions functions can be set
with theSenda P:
1
Test
Test mode, ends after 10 min
2
Auto
Back to automatic mode
5
A
Operation as fully automatic device
6
On
Switch on light
8
15 lux
Brightness setpoint value 15 lux
9
10 lux
Brightness setpoint value 10 lux
10
Lux On
Deactivation of
Brightness measurement
11
800 lux
Brightness setpoint value 800 lux
12
60 s
Lighting time delay 60 s
13
30 s
Lighting time delay 30 s
14
max. Time
max. lighting time delay, 30 min
15
20 min
Lighting time delay 20 min
16
10 min
Lighting time delay 10 min
17
2 min
Lighting time delay 2 min
18
min. Time
min. lighting time delay, 10 s
19
Pulse 1 s
Pulse function
20
500 lux
Brightness setpoint value 500 lux
21
300 lux
Brightness setpoint value 300 lux
22
5 lux
Brightness setpoint value 5 lux
23
min. lux
min. brightness setpoint value, 1 lux
25
Teach-in
Teach in of the brightness setpoint value
26
Off
Switch off lighting
27
Manuell
Semi-automatic operation
30
Reset
Restart of the detector
Settings with Sendo Pro 868-A
Parameters
•
Brightness switching value: 5 – 1000 lux; measurement
off (deactivation of the brightness measurement)
•
Time delay: 30 s – 30 min; pulse (control of staircase
light timer switch)
•
Configuration type: auto (fully automatic device); man
(semi-automatic)
Control commands
•
Teach-in (teach in brightness value)
•
Switching light (on/off light)
•
Presence test (walking test)
•
Restart (restart of the detector)
See also operating manual for Sendo Pro 868-A.
8. Technical data
Operating voltage
110–240 V AC +10 % / –15 %
Frequency
50-60 Hz
Upstream protection device
10 A
Standby output
< 0.5 W
Switching capacity max.
10 A (at 240 V AC, cos
ϕ
= 1)
Switching capacity min.
100 mA/24 V AC/DC
Protection rating
IP 21 (sensor unit), IP 20 (power
supply unit) in accordance with
EN 60529
Protection class
II
Operating temperature
–20 °C … +50 °C
Brightness setting range
5 – 1000 lx
Duty cycle range
30 s – 30 min
Detection angle
360°
Detection area
transversal: min. 8 m (+/– 1 m);
frontal: min. 2 m (+/– 1 m)
Installation height
2 – 4 m
Max. cable length
50 m
Contact
μ contact 240 V AC (NO contact)
Incandescent lamp load
2000 W
Halogen lamp load
2000 W
Fluorescent lamps (LLB low-loss
ballasts):
uncompensated
series compensated
parallel compensated
2000 VA
2000 VA
1300 W (140 µF)
Fluorescent lamps (EB – Electronic
Ballasts)
1200 W
Compact fluorescent lamps (EB)