6.1.3 Determining the setpoint value
6.1.3.1
Calculating the setpoint value in heating operation
Base setpoint value and current setpoint value
Table 31: Current setpoint value during heating
Operating mode
Current setpoint value
Comfort
Standby
Base setpoint value +/- setpoint value offset – reduction in standby mode
Night
Base setpoint value +/- setpoint value offset – reduction in night mode
Frost / heat
protection
configured setpoint for frost protection mode
Example:
Heating in comfort mode.
Parameter page
Parameters
Setting
Setpoint values
Basic setpoint value after
loading the application
21 °C
Reduction in standby
operating mode
(during heating)
2 K
Maximum valid setpoint
value offset
+/- 2 K
The set point value was previously increased by 1 K via object 1.
Calculation:
Current setpoint value
= base se setpoint offset
= 21 °C + 1K
= 22°C
If operation is switched to standby mode, the
Current setpoint = base se setpoint offset – reduction in standby mode
= 21 °C + 1K – 2K
= 20 °C