MIX 2 series RMG 4 U / RME 4 U actuators
6.2.4 Important parameter settings
Standard or customer-defined parameter settings apply for unlisted parameters.
Table 25: RMG 4 U
Parameter page
Parameter
Setting
General
Type of basic module
RMG 4 U
RMG 4 U channel C1:
Configuration options
Channel function
Switching ON/OFF
Activate hour counter
Yes..
Contact characteristics
Type of contact
NO contact
Hour counter and service
Type of hour counter
Counter for time period before
next service
Service interval
(0..2000, x10 h)
200
Reporting of time to service
when changing
(0..100 h, 0 = no report)
100
Report service cyclically
yes
Table 26: VARIA
Parameter page
Parameter
Setting
Selection of display pages
Show page 1 for display objects
yes
Display objects page 1
Fade in operating instructions
on page 1
No
Page heading
Lamp maintenance*
Page 1, line 1
Line format
16 bit counter value object type
Text for line 1
Service in*
Unit for display object
h
Value range
Negative and positive numbers
Display before receipt of value
Read from object via bus
Page 1, line 2
Line format
Switch on object type
Text for line 1
Lamp status*
Text for object value = 0
OK*
Text for object value = 1
Service*
Display before receipt of value
Read from object via bus
*Suggested text