Blinds and switch actuator RMG 8, blinds actuator JMG 4
and switch actuator module RME 8 - EIB
theben
As of: Apr-06 (Subject to change without notice)
Page 17 of 36
3.4.2 Drives
General
Table 1-2: Parameters on the "Drives general" tab
Designation
Values
Description
Security 1 – 3 (objects) without cyclical monitoring
with cyclical monitoring
The last telegram always
determines the security status.
If a security object has been
assigned an important alarming
function, a check is performed
whether the alarm sensor sends data
periodically.
If the sender fails, the security
status is taken up.
Example (see below).
Cyclical monitoring of
all 3 Objects 1 ... 255
[x 1min]
Input: 1 to 255
If the sensors connected to the
security objects send cyclically, the
cycle time, i.e. the time interval
between 2 telegrams must be
entered here.
Recommendation: The monitoring
time of the actuator must be twice
as long as the cycle time of the
device to be monitored.
Example:
If the air speed meter sends to the
security object 1 every 5 minutes,
set the monitoring time to 10
minutes.
Allocation of the 0%
Position to the objects
Slats [%]
0% corresponds to travel down
position
0% corresponds to travel up position
Input of the reference position for
calculating the slats turn.
User level for drives
Standard
Expert
Only standard parameters for
standard use.
On the expert level, the blinds
actuator can be precisely adjusted
in relation to the drives. Thus,
utmost positioning accuracy can be
attained.
Standard parameters for the "expert" user level