Alarm Parameter setting is similar to the Basic    

Parameters setting in [Fig3] except the access code 

is 0001 instead of 0089

 

[Fig3] Basic Parameter setting flow chart

 

The Sensor Connection

 

 

42690 Woodward Avenue, Suite 200

 

Bloomfield Hills, MI 48304 USA

 

 

Tel:  248

-

636

-

1515  [email protected]

 

04

-

2018

 

Page 2 of 2

 

TheSensorConnection.com

 

  Note 4: Relay action setting (PMD

-

A meter does not contain J2 relay.  Its 

settings (AH2 & AL2 can be ignored).

 

1)

 

Set AH1=AL1, relay is disabled

 

2)

 

Set AH1>AL1, relay is for high alarm limit.  See [Fig1]

 

3)

 

Set AH1<AL1, relay is for low limit alarm.  See [Fig2]

 

      3. Peak Value          

 

(Press 

SET

” 

key then input code 0037 to enter)

 

  Note 5: Peak function is interlocked.

 

1)

 

When MA is turned off, MA

-

t can

t be set

 

2)

 

When MI is turned off, MI

-

t can

t be set

 

Peak Value setting is similar to the Basic             

Parameters setting in [Fig3] except the access code 

is 0037 instead of 0089

 

Reset the Peak value:

 

The peak values are stored in the memory even 

after the meter is powered off.  To reset them, 

change the display to show MA, MA

-

t, MI, or MI

-

t.  

Then, press & hold 

˄

” 

key for 3 seconds.  The   

display will show 

——

” 

indicating the memory (for 

all four parameters) is reset.  The meter will start to 

catch the new peak after 2 seconds.

 

      4. Retransmit (Analog Output)

 

(Press 

SET

” 

key then input code 0036 to enter)

 

Retransmit setting is similar to the Basic Parameters 

setting in [Fig3] except the access code is 0036  

instead of 0089

 

  Note 6: Output type section.  User can select either 0

-

20 mA or 4

-

20 mA.

 

  Note 7: Output lower limit.  The LED display value when output is at 0 mA or 

4 mA.

 

Example: If you want 100C to output 0 mA then set obL=100

 

  Note 8: Output high limit.  The LED display value when output is at 20 mA.

 

Example: If you want 1000C to output 20 mA then set obH=1000

 

  This number will affect the resolution of the signal

 

D.  Terminal Assignment

 

1)  1 & 2 are for power input

 

2)   2 & 5 are for alarm relay output.  When alarm is turned on, terminals 2 & 5 

are internally connected.  To drive a 24V buzzer, connect one lead of the 

buzzer to the +24V.  Connect the other lead to terminal 5.

 

3)  4 is for display brightness control.  When connecting the illumination signal 

(+12V) to it, the brightness will be synchronized with headlight.  If not connect-

ed, the brightness can still be controlled by 

˄

” 

key.

 

4)  Wire to 6, 7, 8, & 9 depending on the type of signal input.

 

Example:  Use 6 & 7 for EGT thermocouple probe.

 

5)  3 & 10 is for retransmit (analog output).  To change the output from a 

current to a voltage, install a 1% precision resistor between terminal 3 & 10.

 

250

Ω 

resistor = 1~5VDC or 0~5VDC (depending on 

obty

” 

setting) 

 

500

Ω 

resistor = 2~10VDC or 0~10VDC (depending on 

obty

” 

setting) 

 

E.  Application Example

 

     Exhaust Gas Temperature Measurement

 

DC24V

 

DC24V

DC24V

 