3.OD.3B
cAvity / frAminG prEpArAtiOn
MODEL
A
A1
B
C
D
E
F
Y
700 D
700
800
400
700
225/325
200
680
295
850L
850
950
450
700
250/350
220
680
322
1050LL
1050
1150
500
700
300/400
240
680
345
D
C
A1
A
B
F
E
Gather
Front
Back
Gather
Y
Table 1
Fig. 2
JEtmAstEr BOX DimEnsiOns
Drawings Not
To Scale
Dimensions in mm
Fig. 1
firEBOX instAllAtiOn
1. Locate and position firebox, fit and seal gather in cavity using fire cement (exhaust cement) and bolts
(supplied), to the firebox. Note: Pop rivet back of gather to firebox if required (refer to Cross Section).
Earthquake restraints may be positioned by drilling through firebox into the floor protector, in a position
midway beneath the log-pan. Two 6mm dynabolts or similar will suffice. Do not over tighten and deform
firebox.
2. Attach rock wool (supplied) to the sides of the firebox and gather (using fire cement). DO NOT BLOCK
OFF the air entry between the inner flue pipe and flue pipe casing or the air circulation between the vent
holes in the cavity.
3. Refer to Table 2 & Fig 3 for minimum hearth sizes. Please note, a hearth is not required when the floor
surface below the fire is non combustible ie: concrete pavers, etc.
Table 2
minimum cAvity siZE
Refer to Table 2 for the minimum cavity dimensions and temporary lintel height measurements, until the
firebox and flue system is installed.
Note:
Temporary lintel height is measured from finished floor protector
level.
Note:
Wood Installations can be converted to Gas at a later date. Consider running a gas supply to firebox
cavity at the time of construction.
Dimensions in mm
NOTE: Minimum Recess = 40mm / Maximum Recess = 100mm
ALL INSTALLATIONS MUST COMPLY WITH NZS2918:2001
The Fireplace Ltd recommends all installations be carried out by an
S.F.A.I.T (SOLId FUeL AUTHORISed INSTALLeR TeCHNICIAN).
MODEL
A
B + recess
Temporary
Lintel
X min*
Y min*
Z min*
700 D
800
470 + recess
1200
1100
400
75
850L
950
530 + recess
1200
1250
450
75
1050LL
1150
565 + recess
1200
1450
600
75