Texmate, Inc. Tel. (760) 598-9899  •  www.texmate.com

Page 8

DL-40JANUS manual (d0111)

Modbus Addresses for DL-40 Registers

MODICON 

ADDRESS

MODICON 

ADDRESS

TYPE

R/W

MIN.

MAX.

Register

DESCRIPTION

40001

0x0000

UINT16

R

-

-

RELAY

B_0 SP1 Status

B_1 SP2 Status

B_3 SP4 Status

B_2 SP3 Status

B_4 LED1 Status

B_5 LED2 Status

B_7 LED4 Status

B_6 LED3 Status

40002

0x0001

SINT16

R

-1999

9999

INP 

Hexadecimal value of displayed 

value

40003

0x0002

UINT16

R

96/192

-

BAUD

Modbus baud rate stored as 96 

for 9600 or 192 for 19200, set 

by user via menu interface.

40004

0x0003

UINT16

R

1

247

ADDR

Modbus meter address stored as 

a value between 1 - 247, set by 

user via menu interface.

40005

0x0004

UINT16

R

0

2

PARITY

Modbus parity value stored as 

a value of 0 (no parity), 1 (odd 

parity) or 2 (even parity), set by 

user via menu interface.

40011

0x000A

SINT16

R/W

-1999

9999

PRES1

Setpoint 1 setting

40012

0x000B

UINT16

R/W

0

9999

P1DOM

Setpoint 1 DoM setting

40013

0x000C

UINT16

R/W

0

9999

P1DOB

Setpoint 1 DoB setting

40014

0x000D

UINT16

R/W

0

9999

HYST1

Setpoint 1 Hysteresis setting

40015

0x000E

SINT16

R/W

-1999

9999

PRES2

Setpoint 2 setting

40016

0x000F

UINT16

R/W

0

9999

P2DOM

Setpoint 2 DoM setting

40017

0x0010

UINT16

R/W

0

9999

P2DOB

Setpoint 2 DoB setting

40018

0x0011

UINT16

R/W

0

9999

HYST2

Setpoint 2 Hysteresis setting

40019

0x0012

SINT16

R/W

-1999

9999

PRES3

Setpoint 3 setting

40020

0x0013

UINT16

R/W

0

9999

HYST3

Setpoint 3 Hysteresis setting

40021

0x0014

SINT16

R/W

-1999

9999

PRES4

Setpoint 4 setting

40022

0x0015

UINT16

R/W

0

9999

HYST4

Setpoint 4 Hysteresis setting

40023

0x0016

UINT16

R/W

0

3

RLYMOD

Relay activation polarity (H, L, 

disabled, e.g., HHHH)

40024

0x0017

UINT16

R/W

0

4

DP

Decimal Point setting

40025

0x0018

UINT16

R/W

1

4

BRIGHT

Brightness setting

40026

0x0019

UINT16

R/W

-

-

PEAK

Peak (maximum) measured 

value, writing any value resets 

this register

40027

0x001A

UINT16

R/W

-

-

VALY

Valley (minimum) measured 

value, writing any value resets 

this register

40028

0x001B

SINT16

R

-1999

9999

ZERO

(Auto Mode 

Only)

Displayed value for the min-

imum input signal value that 

is applied during Auto Mode 

calibration

40029

0x001C

SINT16

R

-1999

9999

SPAN

(Auto Mode 

Only)

Displayed value for the max-

imum input signal value that 

is applied during Auto Mode 

calibration

40028

0x001B

SINT16

R

-1999

9999

OFST

(Manual Mode 

Only)

Displayed value for the Offset 

in Manual Rescaling Mode

40029

0x001C

SINT16

R

-1999

9999

SCAL

(Manual Mode 

Only)

Displayed value for the Scale in 

Manual Rescaling Mode

40030

0x001D

UINT16

R

N/A

N/A

IZERO

Calibrated “zero” measure-

ment for displayed ZERO in 

Auto Mode, has no meaning in 

Manual mode

40031

0x001E

UINT16

R

N/A

N/A

ISPAN

Calibrated “span” measurement 

for displayed maximum input 

SPAN in Auto Mode, has no 

meaning in Manual mode

Summary of Contents for DL-40JANUS

Page 1: ... 2 Input Module Analog Calibration 15 Input Module Component Glossary14 15 Input Module Calibration 15 16 Input Signal Conditioning Modules 12 14 Lens Cover Metal Surround Case 17 Manual Rescaling 4 Manual Rescaling Procedure 4 Meter Assembly 10 Modbus RTU RS 485 Settings 7 Modbus RTU Implementation 7 Modbus Address for DL 40 Registers8 Ordering Information 18 Setpoint Relay Configuration Mode 9 S...

Page 2: ...by pressing and releasing the or buttons When there are more than two display selec tions they are shown in brackets below the first display and are also selectable by press ing and releasing the or buttons A dotted box indicates these functions are omitted or bypassed when the related hard ware is not present To explain software programming procedures logic diagrams are used to visually assist in...

Page 3: ... POINT AND BRIGHTNESS SELECTION See Page 6 Setpoint 3 SP3 Setpoint 4 SP4 Valley Offset Scale Factor Calibrate Analog Output Lo Calibrate Analog Output Hi X XXX XX XX XXX X XXXX XXXX 2 3 4 Decimal Point dp Display Brightness br TWO POINT ANALOG OUTPUT CALIBRATION SEE PAGE 6 MANUAL RESCALING MODE See Page 4 SELECTION FOR ANALOG RANGE OUTPUT See Page 6 confirm SP4 confirm confirm confirm This menu on...

Page 4: ... STEP B Select Between Calibration of Input or Output Note If the analog output option is not present Step B is skipped and the program goes directly from Step A to Step C 1 Press the or button to select the display toggling from CAL to inPt 2 Press the P button Display toggles between oFSt and the previous offset setting STEP C Set the Offset on the Digital Display 1 Using the and buttons adjust ...

Page 5: ...Point Analog Output Note If the analog output option is not present Step B is skipped and the program goes directly from Step A to Step C 1 Press the or button to select the display toggling from CAL to inPt input calibration 2 Press the P button Display toggles between ZErO and the previous zero setting STEP C Set the Meter s Low Input Signal Reading on the Digital Display 1 Apply a zero or low s...

Page 6: ...s the P and buttons at the same time Display toggles between CAL and oFF 2 Press the P button Display shows previous dP selection STEP E Set the Decimal Point 1 Using the and adjust the display to the desired decimal point setting 2 Press the P button Display toggles between br and the previous br setting STEP F Set the Display Brightness 1 Using the and buttons adjust the display to the desired b...

Page 7: ...nts and does not include the deci mal point If you need the decimal value with decimal point you will need to read the register convert it to decimal read 40024 see below to determine decimal location then combine the two Display counts are in Two s Complement notation a Hex values for 0 to 9999 are 0x0000 to 0x270F b Hex values for 1 to 1999 are 0xFFFF to 0xF831 c Over range is indicated by a ret...

Page 8: ...ST2 Setpoint 2 Hysteresis setting 40019 0x0012 SINT16 R W 1999 9999 PRES3 Setpoint 3 setting 40020 0x0013 UINT16 R W 0 9999 HYST3 Setpoint 3 Hysteresis setting 40021 0x0014 SINT16 R W 1999 9999 PRES4 Setpoint 4 setting 40022 0x0015 UINT16 R W 0 9999 HYST4 Setpoint 4 Hysteresis setting 40023 0x0016 UINT16 R W 0 3 RLYMOD Relay activation polarity H L disabled e g HHHH 40024 0x0017 UINT16 R W 0 4 DP ...

Page 9: ...P2 Delay on Make doM Delay Time Setting STEP H Set the SP2 Delay on Break dob Delay Time Setting STEP I Set the Hysteresis Setting for Setpoint 2 1 Using the and buttons adjust the display to the desired hysteresis HYSt value 2 Press the P button Display toggles between SP3 and the previous SP4 setting STEP J Set Setpoint 3 SP3 No doM or dob 1 Using the and buttons adjust the display to the desire...

Page 10: ...16 19 19 18 MANUAL rescaling ON AUTO scaling OFF ON SP1 NO SP1 NO SP2 NO SP2 NO Pins 14 and 15 AC DC Power Input Auto sensing AC DC power supply For voltages between 85 265 V AC 95 370 V DC PS1 or 18 48 V AC 10 72 V DC PS2 Pin 14 AC DC Neutral Neutral power supply line Pin 15 AC DC line Live power supply line Analog and RS 485 Output Board Pins Pins 16 and 17 Analog Output Pin 16 Positive analog o...

Page 11: ...n Isolated 9A Form C Relays 29 28 27 25 26 24 23 22 DL Series Options Order Code OR51 OR52 OR53 OR54 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 Relay Modules with 4 Independent 400V 210mA DC only SSRs 29 28 27 25 26 24 23 22 DL Series Options Order Code OR31 OR32 OR33 OR34 4A 4A 4A 4A 4A 4A 4A 4A 4A 4A SP4 SP3 SP2 SP1 SP1 SP2 SP3 SP4 Relay Modules w...

Page 12: ...n are designed to be header selectable by the user and Texmate s unique WARNING AC and DC input signals and power supply voltages can be hazardous Do Not insert remove or handle modules with live wires connected to any terminal plugs I Series Input Signal Conditioning Modules ID04 DC Amps 5A DC ID09 DC Amps 1A DC DC AMPS LO RANGE HI Increase Span Decrease LEOPARD LYNX TIGER Fully User Scalable 065...

Page 13: ...ble PIN 2 _ 091E I Series Input Signal Conditioning Modules Direct Pressure IGYX IGYY IGYZ Ordering Code Options I G For Single Channel IGYX with two digital inputs the last digit of order code is always X For Universal Direct Pressure IGYZ the last digit of order code is always Z 1 psi Absolute Sensor Range CH1 Order Code CH2 Order Code 1 psi Differential 5 psi Absolute 5 psi Differential 15 psi ...

Page 14: ...les at 25 C J 2 C 1 digit typical J 4 F 1 digit maximum K 3 C 1 digit typical K 5 F 1 digit maximum LEOPARD LYNX TIGER IT01 LINEARITY ZERO SPAN 272D For higher accuracy digitally linearized RTD P385 or P392 and Thermocouples J K R and T see the special Leopard Temperature meters DL 40 RTD and DL 40 RTD which use only two special thermocouple modules which are not compatible with regular Leopard Fa...

Page 15: ...le Calibration Examples LO RANGE HI RANGE 10 SPAN Pot 10 10 10 10 10 Signal Span 20 30 40 50 1 SPAN Adjust Header position Span Adjust Header Span Adjust Header Span Range Header 2 3 4 5 10 10 10 10 10 60 70 80 90 100 1 2 3 4 5 Decrease Span Increase 1 2 3 4 5 Decrease Span Increase 1 2 3 4 5 Equivalent Circuit Acts like a 150 Turn Potentiometer Low Range High Range Input LO Input HI HI LO Increas...

Page 16: ...nd adjust the ZERO pot until the display reads 100 Apply 5 V and check that the display reads 1500 Example C 4 to 20 mA to read 00 0 to 100 0 Signal Span 16 mA Digital Display Span 1000 counts 1 The full scale Signal Span of the Process Input 4 20 mAmodules is 0 to 20 mA for a full scale Digital Display Span of 0 to 2000 counts This will provide a digital display of 1000 counts with an input of on...

Page 17: ...se is made from fire retardant polycar bonate A metal surround case can be ordered to enhance the meter s fire retardant capabilities and also provide shielding against electromagnetic interference EMI The metal case slides over the polycarbonate case and is held firmly in place by spring type non return clips The Metal Surround Case must be factory installed on the polycarbonate case and once ins...

Page 18: ...LED Faceplate NEMA 4 Factory install 76 DL40LG N4 Touch Large Green LED Faceplate NEMA 4 Factory install 76 DL40LR N4 Touch Large Red LED Faceplate NEMA 4 Factory install 76 DL40R N4 Touch Red LED Faceplate NEMA 4 Factory install ART FS S D NRC for artwork set up Faceplate Desc ART FS 001 Install Custom Faceplate per meter 1 color OP MTLCLIP Screw Mounting Clips 2 pc to screw tighten slide bracket...